86
| INSTRUCTIONS FOR USE
OM 402PID
SETTING
PROFI
6.
6.5.3
SETTING OF PROGRAMMING STEPS
CHANNE.
PROG.
OUTPUT.
PROG. 1
PROG. 3
PROG. 4
INPUTS
PROG. 5
PROG. 2
PROG.14.
SERVIC.
STEP. 1
STEP. 2
STR. 1
PGM. 1
DAT. 1
TIME 1
DAY. 1
STEP. 64
TYP. ST.
VALUE
STEP. 3
TIME
STEP. 1
Setting of step “1”
TYP. ST.
Selecting the type of
the step
OFF
Ending the control process
- without the setting of “
VALUE
” and “
TIME
”
FIX
Switches over to the control
to the set
-
set value is set in menu
CHANNE. > CONTR.
> SETPO.
- without the setting of “
VALUE
” and “
TIME
”
JUMP
Rapid change
- set value is set under “
VALUE
” If it is not
reached within “
TIME
” an error message “
Err.P
“
is displayed.
STEADY
Maintaining the value
- for the duration specified by “
TIME
” the output
value is controlled to “
VALUE
”
RAMP.
Value increasing over time
- value is corrected automatically so it reaches
preset “
VALUE
” over “
TIME
”
GO TO
Jump within program
- v menu “
CAS
” lze nastavit skok v programu na
žádanou pozici Hodiny = číslo kroku, Minuty =
číslo programu, Sekundy jsou bez významu
- in menu “
TIME
” it is possible to set a jump in
the program to desired position Hours = number
of a step, minutes = number of a program,
seconds have no significance
- without the setting of “
VALUE
”
DAT. 1
Setting the date when the
program is to be launched
- setting in range: 01.01.00…31.12.99
TIM. 1
Setting the time when the
program is to be launched
- setting in range: 00.00.00…23.59.59
Summary of Contents for OM 402PID
Page 17: ...INSTRUCTIONS FOR USE OM 402PID 17 SETTING LIGHT 5 ...
Page 37: ...INSTRUCTIONS FOR USE OM 402PID 37 5 SETTING LIGHT ...
Page 47: ...INSTRUCTIONS FOR USE OM 402PID 47 6 SETTING PROFI ...
Page 59: ...INSTRUCTIONS FOR USE OM 402PID 59 6 SETTING PROFI ...
Page 87: ...INSTRUCTIONS FOR USE OM 402PID 87 6 SETTING PROFI ...
Page 98: ...98 INSTRUCTIONS FOR USE OM 402PID NOTE ...