INSTRUCTIONS FOR USE
OM 402PID
|
73
6.
SETTING
PROFI
6.3.2c
SELECTION OF TYPE OF OUTPUT
6.3.2d
SETTING VALUES FOR LIMITS EVALUATION
PROG.
CHANNE.
SERVIC.
OUTPUT.
LIMITS
AN. OUT.
DATA
DISP.
INPUTS MENORY
LIM 3
LIM 2
LIM 1
LIM 4
INP. L.1
MOD. L.1
TYP. L.1
LIM. L.1
HYS. L.1
ON L.1
OFF L.1
TIM. L.1
CLOSE
OPEN
DEF
TYP. L.1
Selection of type of output
CLOSE
Output switches on when
condition is met
OPEN
Output switches off when
condition is met
Setting is identical for
LIM 1
,
LIM 2
,
LIM 3
and
LIM 4
!
PROG.
CHANNE.
SERVIC.
OUTPUT.
LIMITS
AN. OUT.
DATA
DISP.
INPUTS MENORY
LIM 3
LIM 2
LIM 1
LIM 4
INP. L.1
MOD. L.1
TYP. L.1
LIM. L.1
HYS. L.1
ON L.1
OFF L.1
TIM. L.1
T. TOT.
T. OFF
T. ON
INSENS.
LIM. L.1
Setting limit for switch-on
- for type “
HYSTER
”
HYS. L.1
Setting hysteresis
- for type “
HYSTER
”
- indicates the range around the limit (in both
directions, LIM. ±1/2 HYS.)
ON L.1
Setting the outset of the
interval of limit switch-on
- for type “
FROM..
”
OFF L.1
Setting the end of the
interval of limit switch-on
- for type “
FROM..
”
TIM. L.1
Nastavení časového sepnutí
limity
- for type “
HYSTER.
”, “
PROG.
” and “
READY
”
- setting within the range: ±0…99,9 s
- only for type “
HYSTER.
”
- positive time > relay switches on after
crossing the limit (
LIM. L.1
) and the set time
(
TIM. L.1
)
- negative time > relay switches off after
crossing the limit (
LIM. L.1
) and the set negative
time (
TIM. L.1
)
Setting is identical for
LIM 1
,
LIM 2
,
LIM 3
and
LIM 4
!
Summary of Contents for OM 402PID
Page 17: ...INSTRUCTIONS FOR USE OM 402PID 17 SETTING LIGHT 5 ...
Page 37: ...INSTRUCTIONS FOR USE OM 402PID 37 5 SETTING LIGHT ...
Page 47: ...INSTRUCTIONS FOR USE OM 402PID 47 6 SETTING PROFI ...
Page 59: ...INSTRUCTIONS FOR USE OM 402PID 59 6 SETTING PROFI ...
Page 87: ...INSTRUCTIONS FOR USE OM 402PID 87 6 SETTING PROFI ...
Page 98: ...98 INSTRUCTIONS FOR USE OM 402PID NOTE ...