SELECTION OF TYPE OF LIMIT
PROG.
CHANNE.
SERVIC.
OUTPUT.
LIMITS
AN. OUT.
DATA
DISP.
INPUTS MENORY
LIM 3
LIM 2
LIM 1
LIM 4
INP. L.1
MOD. L.1
TYP. L.1
LIM. L.1
HYS. L.1
ON L.1
OFF L.1
TIM. L.1
HYSTER
TWO-ST.
FROM. .
DEF
READY
PROGR.
PWM
T. TOT.
T. OFF
T. ON
INSENS.
MOD. L.1
Selection the type of limit
HYSTER
Limit is in mode “Limit,
hysteresis, delay”
- for this mode the parameters of “
LIM. L.1
” are
set, at which the limit will shall react, “
HYS. L.1
”
the hysteresis range around the limit
(LIM ±1/2 HYS) and time “
TIM. L.1
” determining
the delay of relay switch-on
FROM. .
Frame limit
- for this mode the parameters are set for interval
“
ON. L.1
” the relay switch-on and “
OFF. L.1
” the
relay switch-off
TWO-ST.
Dvoustavový výstup
(Only LIM 3 and LIM 4)
- If deviation is negative (
INCREASE
),
L3 switches on.
- If deviation is positive, (
DECREASE
)
L4 switches on
PWM
Pulse width modulation
(Only LIM 3 and LIM 4)
- If deviation is negative (
INCREASE
),
L3 switches on
- If deviation is positive, (
DECREASE
)
L4 switches on
PROGR.
indicates the running of the
program (Only LIM 2)
- relay is activated permanently after the
completion of the program if the time is set
to “
0
”, otherwise it is activated for a period
specified in “
TIM. L.2
”
READY
Behavior of relay when the
requested value is reached
(Only Lim 1)
- relay is engaged when the requested value is
reached for the first time, it disengages when
the requested value changes
- relay is activated permanently after reaching
the requested value if the time is set to “
0
”,
otherwise it is activated for a period specified
in “
TIM. L.1
”
Setting is identical for
LIM 1
,
LIM 2
,
LIM 3
and
LIM 4
!
Summary of Contents for OM 402PID
Page 17: ...INSTRUCTIONS FOR USE OM 402PID 17 SETTING LIGHT 5 ...
Page 37: ...INSTRUCTIONS FOR USE OM 402PID 37 5 SETTING LIGHT ...
Page 47: ...INSTRUCTIONS FOR USE OM 402PID 47 6 SETTING PROFI ...
Page 59: ...INSTRUCTIONS FOR USE OM 402PID 59 6 SETTING PROFI ...
Page 87: ...INSTRUCTIONS FOR USE OM 402PID 87 6 SETTING PROFI ...
Page 98: ...98 INSTRUCTIONS FOR USE OM 402PID NOTE ...