INSTRUCTIONS FOR USE
OM 402PID
|
91
9.
ERROR STATEMENTS
ERROR
CAUSE
ELIMINATION
E. d. Un.
Number is too small (large negative) to be displayed
change DP setting, channel constant setting
E. d. Ow.
Number is too large to be displayed
change DP setting, channel constant setting
E. t. Un.
Number is outside the table range
increase table values, change input setting
(channel constant setting)
E. t. Ow.
Number is outside the table range
increase table values, change input setting
(channel constant setting)
E. I. Un.
Input quantity is smaller than permitted input quan-
tity range
change input signal value or input (range) setting
E. I. Ow.
Input quantity is larger than permitted input quantity
range
change input signal value or input (range) setting
E. Hw.
A part of the instrument does not work properly
send the instrument for repair
E. EE
Data in EEPROM corrupted
perform restoration of manufacture setting, upon repeated
error statement send instrument for repair
E.. SET.
Data in EEPROM outside the range
perform restoration of manufacture setting, upon repeated
error statement send instrument for repair
E. CLR
Memory was empty (presetting carried out)
upon repeated error statement send instrument for repair,
possible failure in calibration
E.. OUT.
Analogue output current loop disconnected
check wire connection
Summary of Contents for OM 402PID
Page 17: ...INSTRUCTIONS FOR USE OM 402PID 17 SETTING LIGHT 5 ...
Page 37: ...INSTRUCTIONS FOR USE OM 402PID 37 5 SETTING LIGHT ...
Page 47: ...INSTRUCTIONS FOR USE OM 402PID 47 6 SETTING PROFI ...
Page 59: ...INSTRUCTIONS FOR USE OM 402PID 59 6 SETTING PROFI ...
Page 87: ...INSTRUCTIONS FOR USE OM 402PID 87 6 SETTING PROFI ...
Page 98: ...98 INSTRUCTIONS FOR USE OM 402PID NOTE ...