F-5500 Thermal Mass Flow Meter Manual 06/17 - 2030 / 107023
Page 72
Model F-5500
COMMUNICA
TIONS
COMMUNICA
TIONS
BACnet Programming
BACnet
Communication
Parameters
Selections are:
“9600”
“19200”
“38400”
“57600”
“76800”
“115200"
Next select the MS/TP Mac address. The selection is from 0-127. Please note
that only one device can be on a MS/TP Mac address.
F1 F2 F3 F4
Next select the MS/TP Max Master using
CHG (F1)
. The selection is from
0-127. Press
OK (F4)
to accept the setting.
F1 F2 F3 F4
Next input the device object instance using
CHG (F1)
. Selection is from
0-4194303. Press
OK (F4)
to accept the setting.
F1 F2 F3 F4
Next enter the device object name (9 characters maximum) using
CHG (F1)
.
Press
OK (F4)
to accept the setting.
F1 F2 F3 F4
NOTE: Power cycle is required for the new settings to take effect.
i
MAC_ADD=23
CHG OK
NAME=F-5500_FLOW
CHG OK
ID=12531
CHG OK
MAX_MASTER=127
CHG OK