Instructions for Inline Flow Meter Placement
Install the Model F-5500 Inline style flow meter so that it is far enough away from
bends in the pipe, obstructions, or changes in line sizes to ensure a consistent flow
profile. Review the straight run requirements table on p. 27.
The Model F-5500 is threaded or flanged to the customer’s pipe. Care should be
taken to ensure that the diameter of the mating pipe is the same diameter as the Model
F-5500 flow body or errors in flow readings can occur. The installation procedure
should be a combination of the end user’s best engineering practices, in compliance
with local codes, and the manufacturer’s recommendations.
See "Fig. 2.11: Straight Run Requirements for Upstream Obstructions - Inline" on page
27 for a detailed look at upstream and downstream pipe diameters for inline meters.
Fig. 2.10: Upstream and Downstream Pipe IDs for Inline Meters
Flow Meter
Placement
Inline Type
Installation: Inline Type
Flow Body
Orientation
Inline Type