After pressing
OK (F4)
to accept the Flow unit the display will prompt for the
temperature unit setting:
F1 F2 F3 F4
Press
NXT (F1)
to change selection and
OK (F4)
to accept.
Selections for Temperature units are:
Deg C
Deg F
After pressing
OK (F4)
to accept the temperature unit setting, the display will prompt
for temperature reference in selected unit.
F1 F2 F3 F4
Press
CHG (F1)
to change the reference and
OK (F4)
to accept.
After pressing
OK
(F4)
to accept the reference temperature, the display will prompt for
the reference pressure unit selection:
F1 F2 F3 F4
Press
NXT (F1)
to select next entry and OK (F4) to accept.
Selections are:
mmHG
Millimeters of mercury (absolute)
Psia
Pounds per square inch absolute
bara
Bar absolute
After the pressure unit selection is made, the display will show a menu to enter the
reference pressure:
F1 F2 F3 F4
11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax +1 (727) 442-5699 • [email protected]
F-5500 Thermal Mass Flow Meter Manual 06/17 - 2030 / 107023
Page 50
Model F-5500
OPERA
TION
PresRef= 14.7
CHG OK
PRES UNT= Psia
NXT OK
Reference
Pressure
Operation: Programming
TMP UNT= Deg F
NXT OK
TmpRef = 60
°
F
CHG OK
Temperature
Units
Reference
Temperature
Pressure Units