Powered Pulse:
This type of output refers to a pulse which has an associated voltage with it (see fig. 2).
set the selector switch, s1 to Pwrd Pulse. The allowable voltage range is 5-24 VDC. The
input impedance is set at the factory to be 11 kOhM via the impedance selector jumper
(J1, see fig. 1). a lower impedance, 3 kOhM can be selected if required by the instrument
providing the pulse output. Consult the instrument manufacturer or ONICON if you are
uncertain as to the proper jumper selection.
fig. 2
Open Collector (Sourcing):
This type of output refers to an open Collector switch configured for a sourcing function
(see fig. 3). set the selector switch, s1 to sRC. The switch must be rated for at least 20ma
at 20VDC.