33
V400-R1CF/R1CS
User’s Manual
Section
2
Wiring and
Connection
Section 2
Introduction Procedure
Settings on the reader
Specify the settings as follows to establish communication with the programmable
controller.
Settings on OMRON programmable controller CS1
For information about the detailed setting method, refer to the operation manual of your
programmable controller.
Program controller system settings - Details
* 0
×
00 means a hexadecimal number, and “0” means a binary number.
Setting item
Setting content
Command
Communication speed
9600 bps
(Factory default setting)
Data length
8 bits
(Factory default setting)
Parity
None
(Factory default setting)
Stop bit
1 bit
(Factory default setting)
Header
None
(Factory default setting)
Footer
CR
(Factory default setting)
Reading valid time
T 2 sec.
(Factory default setting)
Process failed reading
Transmits “NL” when no label is found
Transmits “ND” when reading has failed
TH0N0L
TI0N0D
Setting item
Setting content
Dip switch of CPU unit
OFF
Program controller system settings
160[830E]
161[0006]
162[0000]
164[000D]
165[0100]
DM setting
Set [1B5A] to DM00100
(Memorize “[ESC]Z” of the ASCII code)
160
b15
Presence of the arbitrary
communication setting
“1”
Arbitrary setting
b11-8
Serial communication mode “11”
Nonprocedural
b3
Data length
“1”
8 bits
b2
Stop bit
“1”
1 bit
b1-0
Parity
“01”
None
161
b7-0
Communication speed
0
×
06
9600 bps
162
b15-0
Transmission delay time
0
×
0000
No delay
164
b15-8
Start code
0
×
00
None
b7-0
End code
0
×
0D
CR
165
b12
Presence of the start code
“0”
None
b9-8
Presence of the end code
“01”
The end code is present