Chapter 4
4-25
Operation
• If using an External Regeneration Resistor or External Regeneration Resistance Unit, set the
regeneration absorption capacity. Set the regeneration absorption capacity for when the tempera-
ture rises above 120
°
C, not the nominal capacity. (Refer to 3-3-3 Regenerative Energy Absorption
by External Regeneration Resistance for details.)
• Un00A (regeneration load monitor) calculations and detection of A.92 (regeneration overload warn-
ing) and A.32 (regeneration overload alarm) are based on Pn600.
Note If an External Regeneration Resistor or External Regeneration Resistance Unit is not con-
nected, set Pn600 to 0.
Pn600
Regeneration resistor capacity
Settings
0 to max. for
model
Unit
×
10W
Default
0
Restart?
---