24
SmartController EX User's Guide
11069-000 Rev. H
3.2 Connecting Power
-
+
-
+
SmartController EX
24 VDC, 5A
1
2
6
5
4
3
Figure 3-7. User-Supplied Shielded Power Cable
Table 3-6. User-Supplied Shielded Power Cable Description
Item
Description
1
User supplied connector
2
Shield from cable, star washer M3 x 6 screw
3
Optional fuse
4
Frame ground
5
Shield from cable to frame ground on power supply
6
User-provided power supply
DC Power Connectors
The SmartController EX motion controller is equipped with two DC power connectors. DC
power can be applied to either the XDC1 or XDC2 connector.
!
CAUTION:
Use only one 24 VDC power supply per circuit. Failure to do this
could result in damage to the equipment.
!
CAUTION:
The SmartVision MX vision controller has a higher current
demand and should be wired independently. Do not daisy-chain its power
from a SmartController EX motion controller.
NOTE:
The power switch on the SmartController EX motion controller will shut
down just the controller. The two connectors, XDC1 and XDC2, are always con-
nected to each other, so any device that receives power from XDC1 or XDC2 will
maintain power after the controller is shut down.
Chassis Grounding
The SmartController EX motion controller is equipped with a grounding point, as shown in
the following figure. We recommend connecting a ground wire from the grounding point on