S8VK-S

20

 Recommended Ferrules and Crimping Tools

Recommended ferrules

S8VK-S03024, S06024, S12024, S24024: Input and Output Terminals
S8VK-S48024: Input Terminals
S8VK-S24024, S48024: Low-voltage detection output Terminals

Note: 1.

Make sure that the outer diameter of the wire is smaller than 
the inner diameter of the insulating sleeve of the 
recommended ferrule.

2.

Make sure that the ferrule processing dimensions conform 
to the following figure.

S8VK-S48024: Output Terminals

Note: 1.

Make sure that the outer diameter of the wire is smaller than 
the inner diameter of the insulating sleeve of the 
recommended ferrule.

2.

Make sure that the ferrule processing dimensions conform 
to the following figure.

Recommended Flat-blade Screwdriver

Use a flat-blade screwdriver to connect and remove wires.
Use the following flat-blade screwdriver.
The following table shows manufacturers and models as of 2015/Dec.

Power Boost Function

The boost current is a temporary current that exceeds the rated 
current. 
However, it should meet the following four boost current conditions.

• Time that the boost current flows: t1 

 10 s

• The boost current: Ip 

 Maximum boost current

• The average output current: Iave 

 Rated output current

• The time ratio of the boost current flow: Duty 

 30%

• Do not allow a boost current to flow for more than 10 s.

Do not allow the duty to exceed 30%. These conditions may 
damage the Power Supply.

• Do not allow the average current for one cycle of the boost current 

to exceed the rated current. The Power Supply may be damaged.

• Derate the boost current and the average output current loads 

according to the ambient operating temperature and mounting 
direction.

Overcurrent Protection

• Internal parts may possibly deteriorate or be damaged if a 

short-circuited or overcurrent state continues during operation.

• Internal parts may possibly deteriorate or be damaged if the Power 

Supply is used for applications with frequent inrush current or 
overloading at the load end. Do not use the Power Supply for such 
applications.

Applicable wire

Ferrule

Conductor

length

(mm)

Stripping 

length

(mm)

(Ferrules used)

Recommended ferrules

(mm

2

)

(AWG)

Manufactured by 
Phoenix Contact

Manufactured 

by Weidmuller

Manufactured by 

Wago

0.25

24

8

10

AI 0,25-8

H0.25/12

FE-0.25-8N-YE

10

12

AI 0,25-10

---

---

0.34

22

8

10

AI 0,34-8

H0.34/12

FE-0.34-8N-TQ

10

12

AI 0,34-10

---

---

0.50

20

8

10

AI 0,5-8

H0.5/14

FE-0.5-8N-WH

10

12

AI 0,5-10

H0.5/16

FE-0.5-10N-WH

0.75

18

8

10

AI 0,75-8

H0.75/14

FE-0.75-8N-GY

10

12

AI 0,75-10

H0.75/16

FE-0.75-10N-GY

1/1.25

18/17

8

10

AI 1-8

H1.0/14

FE-1.0-8N-RD

10

12

AI 1-10

H1.0/16

FE-1.0-10N-RD

1.25/1.5 17/16

8

10

AI 1,5-8

H1.5/14

FE-1.5-8N-BK

10

12

AI 1,5-10

H1.5/16

FE-1.5-10N-BK

2.5

14

10

12

AI 2,5-10

H2.5/16DS FE-2.5-10N-BU

Recommended crimp tool

CRIMPFOX6
CRIMPFOX6-F
CRIMPFOX10S

PZ6 roto

Variocrimp4

Applicable wire

Ferrule

Conductor

length

(mm)

Stripping 

length

(mm)

(Ferrules used)

Recommended ferrules

(mm

2

)

(AWG)

Manufactured by 
Phoenix Contact

Manufactured 

by Weidmuller

Manufactured by 

Wago

4

12

12

14

AI4-12

H4.0/
20D

FE-4.0-12N-GY

6

10

12

16

AI6-12

H6.0/20

FE-6.0-12N-Ye 

*

Recommended crimp tool

CRIMPFOX6
CRIMPFOX6T-F
CRIMPFOX10S

PZ6 roto

Variocrimp4

*

 Use the 
Variocrim
p16.

8 to 10 mm

2.6 mm max.

2.8 mm max.

12 mm

4 mm max.

4 mm max.

Model

Manufacturer

XW4Z-00B

Omron

ESD0.40X2.5

Wera

SZF 0.4X2.5

Phoenix Contact

0.4X2.5X75 302

Wiha

AEF.2.5X75

Facom

210-719

Wago*1

*1.

Insulated types of Flat-blade Screw driver, strongly recommended to 
prevent from an electric shock.

SDI 0.4X2.5X75

Weidmuller

*1

Side

0.4 mm

2.5 mm dia.

2.5 mm

Front

Duty=

t1 + t2

t1

× 100 [%] 

≤ 

30%

[A]

Ip: Boost current

Rated current

lave: Average current

t2

t1

output current

Summary of Contents for S8VK-S Series

Page 1: ...loyd s DNV GL Except 30 W Conforms to SEMI F47 0706 RoHS compliant 1 For front side by side mounting see page 18 Model Number Structure Model Number Legend Note Not all combinations are possible Refer...

Page 2: ...sulation Withstand voltage 3 0 kVAC for 1 min between all input terminals and output terminals current cutoff 10 mA 2 0 kVAC for 1 min between all input terminals and PE terminals current cutoff 10 mA...

Page 3: ...2 0 kVAC for 1 min between all input terminals and PE terminals current cutoff 20 mA 1 0 kVAC for 1 min between all output terminals and PE terminals current cutoff 20 mA 500 VAC for 1 min between al...

Page 4: ...the above table 11 Refer to Recommended Replacement Periods and Periodic Replacement for Preventive Maintenance on page 23 for details 12 Refer to Standard Compliance below Standard Compliance EN IEC...

Page 5: ...othing circuit Overcurrent detection circuit AC L INPUT AC N S8VK S03024 30 W S8VK S06024 60 W V V V V V DC OUTPUT Voltage detection circuit Photocoupler Rectifier smoothing circuit Noise filter Drive...

Page 6: ...etection circuit Voltage detection circuit Overvoltage detection circuit Photocoupler S8VK S24024 240 W Overcurrent detection circuit V V V V V DC OUTPUT Rectifier smoothing circuit Smoothing circuit...

Page 7: ...1 Input terminals Connect the input lines to these terminals 1 2 L2 3 N1 4 N2 5 PE Protective Earth terminal PE Connect the ground line to this terminal 2 6 V1 DC Output terminals Connect the load lin...

Page 8: ...4 Horizontal separation 15 mm or more Note 1 At less than 90 VAC derate the load at 2 5 V 2 For a DC input reduce the load given in the above derating curve by multiplying by the following coefficient...

Page 9: ...e load at 1 V 2 For a DC input reduce the load given in the above derating curve by multiplying by the following coefficients S8VK S48024 0 8 3 In the shaded area time is required to reach the rated o...

Page 10: ...curve by multiplying by the following coefficients S8VK S12024 0 9 Standard mounting 30 60 W S8VK S03024 S8VK S06024 Front Side by side mounting Horizontal separation Less than 15 mm Note 1 Apply the...

Page 11: ...acket 240 W S8VK S24024 Front side by side mounting Horizontal separation Less than 15 mm Note 1 Apply the rated voltage Front Side by side mounting 480 W S8VK S48024 Front side by side mounting Horiz...

Page 12: ...ke below 1 The supplying voltage is below the maximum rated input OMRON Power supply allows the input voltage equivalent or less than 240 VAC 10 Please confirm the input voltage between two lines if t...

Page 13: ...mensions Unit mm Sliding 10 max Rail Stopper 1 2 90 1 86 3 5 5 4 78 55 4 7 90 1 5 4 32 1 S8VK S03024 30 W S8VK S06024 60 W 1 2 3 5 86 90 1 5 4 4 7 55 1 90 1 5 4 78 55 Sliding 10 max Rail Stopper S8VK...

Page 14: ...2 Sliding 8 0 max 5 4 5 7 8 38 1 108 8 19 8 20 4 124 1 122 2 1 117 8 111 4 5 4 S8VK S24024 240 W 10 8 1 2 1 4 0 6 0 6 7 5 5 4 5 18 3 0 9 19 8 20 4 108 8 60 1 111 4 117 8 122 2 1 124 1 5 2 Sliding 8 0...

Page 15: ...at the Unit will be subject to vibration or shock use a steel DIN Rail Otherwise metallic filings may result from aluminum abrasion 4 5 15 25 25 10 10 1 000 500 25 25 15 5 35 0 3 7 3 0 15 27 0 15 1 Va...

Page 16: ...Dimensions Appearance Front mounting bracket For 30 W and 60 W models S82Y VS10F Side mounting bracket For 30 W and 60 W models S82Y VS10S Front mounting bracket For 240 W and 480 W models S82Y VK10F...

Page 17: ...or cuttings resulting from installation work to enter the Product WARNING Indicates a potentially hazardous situation which if not avoided will result in minor or moderate injury or may result in seri...

Page 18: ...ck in direction B To dismount the Block pull down portion C with a flat blade screwdriver and pull out the Block Wiring Connect the ground completely A protective earthing terminal stipulated in safet...

Page 19: ...he angle should be between 10 and 15 If the flat blade screwdriver is inserted correctly you will feel the spring in the release hole 2 With the flat blade screwdriver still inserted into the release...

Page 20: ...iorate or be damaged if a short circuited or overcurrent state continues during operation Internal parts may possibly deteriorate or be damaged if the Power Supply is used for applications with freque...

Page 21: ...Supplies can be connected in parallel You must meet the following conditions to use parallel operation Standard mounting The range of ambient temperature is 25 to 40 C Left and right interval 15 mm o...

Page 22: ...rge occurs while turning ON the power supply In case there is no output voltage please check the following points before contacting us Checking overload protected status Check whether the load is in o...

Page 23: ...re used in the Power Supply and the Power Supply depends on the correct operation of these components to achieve the original Power Supply functions and performance However the influence of the ambien...

Page 24: ...MEMO 24...

Page 25: ...25 MEMO...

Page 26: ...MEMO 26...

Page 27: ...CONNECTED WITH THE PRODUCTS WHETHER SUCH CLAIM IS BASED IN CONTRACT WARRANTY NEGLIGENCE OR STRICT LIABILITY Further in no event shall liability of Omron Companies exceed the individual price of the Pr...

Page 28: ...es IL 60169 U S A Tel 1 847 843 7900 Fax 1 847 843 7787 Regional Headquarters OMRON EUROPE B V Wegalaan 67 69 2132 JD Hoofddorp The Netherlands Tel 31 2356 81 300 Fax 31 2356 81 388 Contact www ia omr...

Reviews: