background image

S8VK-S

19

• With the S8VK-S03024, S8VK-S06024 and S12024 models, do 

not use crossover wiring for more than Power Supplies, and do not 
allow the steady-state current to the input terminals to exceed 5 A.
With the S8VK-S24024 and S48024 models, do not use crossover 
wiring for more than Power Supplies, and do not allow the steady-
state current to the input terminals to exceed 10 A. The table gives 
the recommended wires for one Power Supply.

• If you use crossover wiring for N number of Power Supplies, a 

current that is N times the current for a standalone Power Supply 
may flow to the input terminals. Take this into consideration when 
you select wiring materials.

Stripping length

S8VK-S03024, S06024, S12024, S24024: Input and Output Terminals 
S8VK-S48024: Input Terminals

S8VK-S48024: Output Terminals

S8VK-S24024, S48024: Low-voltage detection output Terminals

 Connecting wires to the Push-In Plus Terminal Block

Part Names of the Terminal Block

Connecting Wires with Ferrules and Solid Wires

Insert the solid wire or ferrule straight into the terminal block until the 
end touches the terminal block.

If a wire is difficult to connect because it is too thin, use a flat-blade 
screwdriver in the same way as when connecting stranded wire.

Connecting Stranded Wires

Use the following procedure to connect the wires to the terminal block.

1.

Hold a flat-blade screwdriver at an angle and insert it into the 
release hole. The angle should be between 10° and 15°.
If the flat-blade screwdriver is inserted correctly, you will feel the 
spring in the release hole.

2.

With the flat-blade screwdriver still inserted into the release hole, 
insert the wire into the terminal hole until it strikes the terminal 
block.

3.

Remove the flat-blade screwdriver from the release hole.

Checking Connections

• After the insertion, pull gently on the wire to make sure that it will 

not come off and the wire is securely fastened to the terminal block.

• If you use a ferrule with a conductor length of 10 mm, part of the 

conductor may be visible after the ferrule is inserted into the 
terminal block, but the product insulation distance will still be 
satisfied.

 Removing wires from the Push-In Plus Terminal

Use the following procedure to remove wires from the terminal.
The same method is used to remove stranded wires, solid wires, and 
ferrules.

1.

Hold a flat-blade screwdriver at an angle and insert it into the 
release hole.

2.

With the flat-blade screwdriver still inserted into the release hole, 
remove the wire from the terminal insertion hole.

3.

Remove the flat-blade screwdriver from the release hole.

Recommended Wire

Stripping length

(Ferrules not used)

0.25 to 1.5 mm

2

/AWG24 to 16

8 mm

2 to 2.5 mm

2

/AWG14

10 mm

Recommended Wire

Stripping length

(Ferrules not used)

3.5  to 6 mm

2

/AWG12 to 10

15 mm

Recommended Wire

Stripping length

(Ferrules not used)

0.25  to 2.5 mm

2

/AWG24 to 14 

10 mm

Release hole

Terminal (Insertion) hole 

Terminal (Insertion) hole 

Ferrules
and solid wires

Release hole

Flat-blade screwdriver

10 to 15°

1

3

2

Flat-blade screwdriver

10 to 15°

1

3

2

Summary of Contents for S8VK-S Series

Page 1: ...loyd s DNV GL Except 30 W Conforms to SEMI F47 0706 RoHS compliant 1 For front side by side mounting see page 18 Model Number Structure Model Number Legend Note Not all combinations are possible Refer...

Page 2: ...sulation Withstand voltage 3 0 kVAC for 1 min between all input terminals and output terminals current cutoff 10 mA 2 0 kVAC for 1 min between all input terminals and PE terminals current cutoff 10 mA...

Page 3: ...2 0 kVAC for 1 min between all input terminals and PE terminals current cutoff 20 mA 1 0 kVAC for 1 min between all output terminals and PE terminals current cutoff 20 mA 500 VAC for 1 min between al...

Page 4: ...the above table 11 Refer to Recommended Replacement Periods and Periodic Replacement for Preventive Maintenance on page 23 for details 12 Refer to Standard Compliance below Standard Compliance EN IEC...

Page 5: ...othing circuit Overcurrent detection circuit AC L INPUT AC N S8VK S03024 30 W S8VK S06024 60 W V V V V V DC OUTPUT Voltage detection circuit Photocoupler Rectifier smoothing circuit Noise filter Drive...

Page 6: ...etection circuit Voltage detection circuit Overvoltage detection circuit Photocoupler S8VK S24024 240 W Overcurrent detection circuit V V V V V DC OUTPUT Rectifier smoothing circuit Smoothing circuit...

Page 7: ...1 Input terminals Connect the input lines to these terminals 1 2 L2 3 N1 4 N2 5 PE Protective Earth terminal PE Connect the ground line to this terminal 2 6 V1 DC Output terminals Connect the load lin...

Page 8: ...4 Horizontal separation 15 mm or more Note 1 At less than 90 VAC derate the load at 2 5 V 2 For a DC input reduce the load given in the above derating curve by multiplying by the following coefficient...

Page 9: ...e load at 1 V 2 For a DC input reduce the load given in the above derating curve by multiplying by the following coefficients S8VK S48024 0 8 3 In the shaded area time is required to reach the rated o...

Page 10: ...curve by multiplying by the following coefficients S8VK S12024 0 9 Standard mounting 30 60 W S8VK S03024 S8VK S06024 Front Side by side mounting Horizontal separation Less than 15 mm Note 1 Apply the...

Page 11: ...acket 240 W S8VK S24024 Front side by side mounting Horizontal separation Less than 15 mm Note 1 Apply the rated voltage Front Side by side mounting 480 W S8VK S48024 Front side by side mounting Horiz...

Page 12: ...ke below 1 The supplying voltage is below the maximum rated input OMRON Power supply allows the input voltage equivalent or less than 240 VAC 10 Please confirm the input voltage between two lines if t...

Page 13: ...mensions Unit mm Sliding 10 max Rail Stopper 1 2 90 1 86 3 5 5 4 78 55 4 7 90 1 5 4 32 1 S8VK S03024 30 W S8VK S06024 60 W 1 2 3 5 86 90 1 5 4 4 7 55 1 90 1 5 4 78 55 Sliding 10 max Rail Stopper S8VK...

Page 14: ...2 Sliding 8 0 max 5 4 5 7 8 38 1 108 8 19 8 20 4 124 1 122 2 1 117 8 111 4 5 4 S8VK S24024 240 W 10 8 1 2 1 4 0 6 0 6 7 5 5 4 5 18 3 0 9 19 8 20 4 108 8 60 1 111 4 117 8 122 2 1 124 1 5 2 Sliding 8 0...

Page 15: ...at the Unit will be subject to vibration or shock use a steel DIN Rail Otherwise metallic filings may result from aluminum abrasion 4 5 15 25 25 10 10 1 000 500 25 25 15 5 35 0 3 7 3 0 15 27 0 15 1 Va...

Page 16: ...Dimensions Appearance Front mounting bracket For 30 W and 60 W models S82Y VS10F Side mounting bracket For 30 W and 60 W models S82Y VS10S Front mounting bracket For 240 W and 480 W models S82Y VK10F...

Page 17: ...or cuttings resulting from installation work to enter the Product WARNING Indicates a potentially hazardous situation which if not avoided will result in minor or moderate injury or may result in seri...

Page 18: ...ck in direction B To dismount the Block pull down portion C with a flat blade screwdriver and pull out the Block Wiring Connect the ground completely A protective earthing terminal stipulated in safet...

Page 19: ...he angle should be between 10 and 15 If the flat blade screwdriver is inserted correctly you will feel the spring in the release hole 2 With the flat blade screwdriver still inserted into the release...

Page 20: ...iorate or be damaged if a short circuited or overcurrent state continues during operation Internal parts may possibly deteriorate or be damaged if the Power Supply is used for applications with freque...

Page 21: ...Supplies can be connected in parallel You must meet the following conditions to use parallel operation Standard mounting The range of ambient temperature is 25 to 40 C Left and right interval 15 mm o...

Page 22: ...rge occurs while turning ON the power supply In case there is no output voltage please check the following points before contacting us Checking overload protected status Check whether the load is in o...

Page 23: ...re used in the Power Supply and the Power Supply depends on the correct operation of these components to achieve the original Power Supply functions and performance However the influence of the ambien...

Page 24: ...MEMO 24...

Page 25: ...25 MEMO...

Page 26: ...MEMO 26...

Page 27: ...CONNECTED WITH THE PRODUCTS WHETHER SUCH CLAIM IS BASED IN CONTRACT WARRANTY NEGLIGENCE OR STRICT LIABILITY Further in no event shall liability of Omron Companies exceed the individual price of the Pr...

Page 28: ...es IL 60169 U S A Tel 1 847 843 7900 Fax 1 847 843 7787 Regional Headquarters OMRON EUROPE B V Wegalaan 67 69 2132 JD Hoofddorp The Netherlands Tel 31 2356 81 300 Fax 31 2356 81 388 Contact www ia omr...

Reviews: