![background image](http://html1.mh-extra.com/html/omron/s8vk-s-series/s8vk-s-series_manual_743720011.webp)
S8VK-S
11
240 W (S8VK-S24024) Horizontal separation: 15 mm or more
Note: 1.
At less than 90 VAC, derate the load at 2.5%/V.
2.
For a DC input, reduce the load given in the above derating
curve by multiplying by the following coefficients.
S8VK-S24024: 0.8
Standard mounting, mounted with Front-mounting Bracket
480 W (S8VK-S48024) Horizontal separation: 15 mm or more
Note: 1.
At less than 100 VAC, derate the load at 1%/V.
2.
For a DC input, reduce the load given in the above derating
curve by multiplying by the following coefficients.
S8VK-S48024: 0.8
Standard mounting, mounted with Front-mounting Bracket
240 W (S8VK-S24024): Front, side-by-side mounting
Horizontal separation: Less than 15 mm
Note: 1.
Apply the rated voltage
Front, Side-by-side mounting
480 W (S8VK-S48024): Front, side-by-side mounting
Horizontal separation: Less than 15 mm
Note: 1.
Apply the rated voltage
Front, Side-by-side mounting
0
500
1,000
1,500
2,000
2,500
3,000
3,500
120
100
80
87
75
60
40
20
0
55°C max
60°C
65°C
70°C
100%
90%
77%
65%
Load r
atio (%)
Altitude (m)
0
500
1,000
1,500
2,000
2,500
3,000
3,500
120
100
80
87
75
60
40
20
0
55°C max
60°C
65°C
70°C
100%
90%
77%
65%
Load r
atio (%)
Altitude (m)
120
100
80
60
40
20
0
0
500
1,000
1,500
2,000
2,500
3,000
3,500
100%
85%
75%
35°C max
40°C
55°C
Load r
atio (%)
Altitude (m)
120
100
80
60
40
20
0
0
500
1,000
1,500
2,000
2,500
3,000
3,500
100%
85%
75%
35°C max
40°C
55°C
Load r
atio (%)
Altitude (m)