background image

S8VK-S

13

Dimensions

(Unit: mm)

(Sliding: 10 max.)

Rail Stopper

(1.2)

90

 ±1

86

3.5

5.4

78.55

4.7

90

 ±1

5.4

32

 ±1

S8VK-S03024 (30 W)
S8VK-S060

24 (

60 W)

(1.2)

3.5

86

90

 ±1

5.4

4.7

55

 ±1

90

 ±1

5.4

78.55

(Sliding: 10 max.)

Rail Stopper

S8VK-S120

24 (

120 W)

Summary of Contents for S8VK-S Series

Page 1: ...loyd s DNV GL Except 30 W Conforms to SEMI F47 0706 RoHS compliant 1 For front side by side mounting see page 18 Model Number Structure Model Number Legend Note Not all combinations are possible Refer...

Page 2: ...sulation Withstand voltage 3 0 kVAC for 1 min between all input terminals and output terminals current cutoff 10 mA 2 0 kVAC for 1 min between all input terminals and PE terminals current cutoff 10 mA...

Page 3: ...2 0 kVAC for 1 min between all input terminals and PE terminals current cutoff 20 mA 1 0 kVAC for 1 min between all output terminals and PE terminals current cutoff 20 mA 500 VAC for 1 min between al...

Page 4: ...the above table 11 Refer to Recommended Replacement Periods and Periodic Replacement for Preventive Maintenance on page 23 for details 12 Refer to Standard Compliance below Standard Compliance EN IEC...

Page 5: ...othing circuit Overcurrent detection circuit AC L INPUT AC N S8VK S03024 30 W S8VK S06024 60 W V V V V V DC OUTPUT Voltage detection circuit Photocoupler Rectifier smoothing circuit Noise filter Drive...

Page 6: ...etection circuit Voltage detection circuit Overvoltage detection circuit Photocoupler S8VK S24024 240 W Overcurrent detection circuit V V V V V DC OUTPUT Rectifier smoothing circuit Smoothing circuit...

Page 7: ...1 Input terminals Connect the input lines to these terminals 1 2 L2 3 N1 4 N2 5 PE Protective Earth terminal PE Connect the ground line to this terminal 2 6 V1 DC Output terminals Connect the load lin...

Page 8: ...4 Horizontal separation 15 mm or more Note 1 At less than 90 VAC derate the load at 2 5 V 2 For a DC input reduce the load given in the above derating curve by multiplying by the following coefficient...

Page 9: ...e load at 1 V 2 For a DC input reduce the load given in the above derating curve by multiplying by the following coefficients S8VK S48024 0 8 3 In the shaded area time is required to reach the rated o...

Page 10: ...curve by multiplying by the following coefficients S8VK S12024 0 9 Standard mounting 30 60 W S8VK S03024 S8VK S06024 Front Side by side mounting Horizontal separation Less than 15 mm Note 1 Apply the...

Page 11: ...acket 240 W S8VK S24024 Front side by side mounting Horizontal separation Less than 15 mm Note 1 Apply the rated voltage Front Side by side mounting 480 W S8VK S48024 Front side by side mounting Horiz...

Page 12: ...ke below 1 The supplying voltage is below the maximum rated input OMRON Power supply allows the input voltage equivalent or less than 240 VAC 10 Please confirm the input voltage between two lines if t...

Page 13: ...mensions Unit mm Sliding 10 max Rail Stopper 1 2 90 1 86 3 5 5 4 78 55 4 7 90 1 5 4 32 1 S8VK S03024 30 W S8VK S06024 60 W 1 2 3 5 86 90 1 5 4 4 7 55 1 90 1 5 4 78 55 Sliding 10 max Rail Stopper S8VK...

Page 14: ...2 Sliding 8 0 max 5 4 5 7 8 38 1 108 8 19 8 20 4 124 1 122 2 1 117 8 111 4 5 4 S8VK S24024 240 W 10 8 1 2 1 4 0 6 0 6 7 5 5 4 5 18 3 0 9 19 8 20 4 108 8 60 1 111 4 117 8 122 2 1 124 1 5 2 Sliding 8 0...

Page 15: ...at the Unit will be subject to vibration or shock use a steel DIN Rail Otherwise metallic filings may result from aluminum abrasion 4 5 15 25 25 10 10 1 000 500 25 25 15 5 35 0 3 7 3 0 15 27 0 15 1 Va...

Page 16: ...Dimensions Appearance Front mounting bracket For 30 W and 60 W models S82Y VS10F Side mounting bracket For 30 W and 60 W models S82Y VS10S Front mounting bracket For 240 W and 480 W models S82Y VK10F...

Page 17: ...or cuttings resulting from installation work to enter the Product WARNING Indicates a potentially hazardous situation which if not avoided will result in minor or moderate injury or may result in seri...

Page 18: ...ck in direction B To dismount the Block pull down portion C with a flat blade screwdriver and pull out the Block Wiring Connect the ground completely A protective earthing terminal stipulated in safet...

Page 19: ...he angle should be between 10 and 15 If the flat blade screwdriver is inserted correctly you will feel the spring in the release hole 2 With the flat blade screwdriver still inserted into the release...

Page 20: ...iorate or be damaged if a short circuited or overcurrent state continues during operation Internal parts may possibly deteriorate or be damaged if the Power Supply is used for applications with freque...

Page 21: ...Supplies can be connected in parallel You must meet the following conditions to use parallel operation Standard mounting The range of ambient temperature is 25 to 40 C Left and right interval 15 mm o...

Page 22: ...rge occurs while turning ON the power supply In case there is no output voltage please check the following points before contacting us Checking overload protected status Check whether the load is in o...

Page 23: ...re used in the Power Supply and the Power Supply depends on the correct operation of these components to achieve the original Power Supply functions and performance However the influence of the ambien...

Page 24: ...MEMO 24...

Page 25: ...25 MEMO...

Page 26: ...MEMO 26...

Page 27: ...CONNECTED WITH THE PRODUCTS WHETHER SUCH CLAIM IS BASED IN CONTRACT WARRANTY NEGLIGENCE OR STRICT LIABILITY Further in no event shall liability of Omron Companies exceed the individual price of the Pr...

Page 28: ...es IL 60169 U S A Tel 1 847 843 7900 Fax 1 847 843 7787 Regional Headquarters OMRON EUROPE B V Wegalaan 67 69 2132 JD Hoofddorp The Netherlands Tel 31 2356 81 300 Fax 31 2356 81 388 Contact www ia omr...

Reviews: