S8VK-S

12

Mounting

*

For front, side-by-side mounting, see page 18.

Overload Protection

For models S8VK-S03024, S8VK-S06024 and S8VK-S12024, the 
output voltage is automatically reduced, and the unit is protected from 
short circuit current and overcurrent damage if the load current 121% 
to 160% of the rated current. For models S8VK-S24024 and S8VK-
S48024, the output voltage is automatically reduced, and the unit is 
protected from short circuit current and overcurrent damage if the 
load current 151% to 165% of the rated current.
When the output voltage returns within the rated range, overload 
protection is automatically cleared.

Note: 1.

Internal parts may occasionally deteriorate or be damaged if a 
short-circuited or overcurrent state continues during operation. 

2.

Internal parts may possibly deteriorate or be damaged if the 
Power Supply is used for applications with frequent inrush 
current or overloading at the load end. Do not use the Power 
Supply for such applications.

Overvoltage Protection

Consider the possibility of an overvoltage and design the system so 
that the load will not be subjected to an excessive voltage even if the 
feedback circuit in the Power Supply fails. If an excessive voltage that 
is approximately 130% of the rated voltage or more is output, the 
output voltage is shut OFF. Reset the input power by turning it OFF 
for at least three minutes and then turning it back ON again.

Note:

Do not turn ON the power again until the cause of the 
overvoltage has been removed.

Inrush Current, Startup Time, Output Hold Time

Note:

Twice the normal inrush current will flow during parallel operation 
or for backup operation.

 

Also, if crossover wiring is used for N 

number of Power Supplies, an inrush current of N times the inrush 
current for a standalone Power Supply will flow.
Therefore, check the fusing characteristics of fuses and 
operating characteristics of breakers making sure that the 
external fuses will not burn out and the circuit breakers will not 
be activated by the inrush current. 

Two phases application for Single phase models

For All Single phase Models, S8VK-S

Basically OMRON single phase power supply can be used on two-
phases of a 3–phase-system when some of conditions satisfy like 
below.

1.

The supplying voltage is below the maximum rated input.
OMRON Power supply allows the input voltage equivalent or less 
than 240 VAC+10%. 
Please confirm the input voltage between two lines if the input 
voltage satisfies this condition before connecting.

2.

The external protector is needed on N input line to secure a safety. 
N line has no protection of a fuse internally. 
An appropriate fuse or circuit breaker should be connected on N 
input line like the following.

Low-voltage detection output (Only for 240 and 
480 W)

Output externally by photo-switch when an output voltage drop is 
detected (OFF when an output drop occurs). The detection voltage is 
set to about 80% (75% to 90%) of the rated output voltage.

Photo-switch

1.

30 VDC max., 50 mA max. Residual voltage 2 V or less when ON. 
Leakage current 0.1 mA or less when OFF.

2.

The low-voltage detection output function monitors the voltage of 
the output terminal of the power supply.
To check the precise voltage state, measure the voltage of the 
load end.

3.

If the set voltage is less than 90% of the rated voltage, the low-
voltage detection function may activate.

4.

The signal output circuit do not contain current-limiting circuit. Do 
not allow the output current to exceed 50 mA.

5.

After you complete the wiring, confirm that operation is correct.

Reference Value

(B) F

a

ce-

u

p mo

u

nting

(A) 

S

t

a

nd

a

rd (Vertic

a

l) 

mo

u

nting

(C) Front, 

S

ide-

b

y-

s

ide 

mo

u

nting 

*

0

50

100

Output current (%)

Output v

oltage (V)

Intermittent operation

S8VK-S03024, S8VK-S06024, 
S8VK-S12024

S8VK-S24024, S8VK-S48024

0

150

100

50

Output current (%)

Output v

oltage (V)

Intermittent operation

90%

96.5%

Startup time

Input
Voltage

Input
Current

Output
voltage

Inrush current on input application

Input OFF

Input ON

Hold time

Reliability 
(MTBF)

Value

Single phase model
30 W: 640,000
60 W: 640,000
120 W: 480,000
240 W: 390,000
480 W: 330,000

Definition

MTBF stands for Mean Time Between 
Failures, which is calculated according to the 
probability of accidental device failures, and 
indicates reliability of devices.
Therefore, it does not necessarily represent a 
life of the product.

Life expectancy

10 yrs. Min.

Definition

The life expectancy indicates average 
operating hours under the ambient 
temperature of 40°C and a load rate of 50%. 
Normally this is determined by the life 
expectancy of the built-in aluminum electrolytic 
capacitor.

An external 
fuse or a  
circuit breaker

max. 240 VAC+10%

Internal 
Fuse

Power Supply

N

L

L

1

L

2

L

3

PE

Summary of Contents for S8VK-S Series

Page 1: ...loyd s DNV GL Except 30 W Conforms to SEMI F47 0706 RoHS compliant 1 For front side by side mounting see page 18 Model Number Structure Model Number Legend Note Not all combinations are possible Refer...

Page 2: ...sulation Withstand voltage 3 0 kVAC for 1 min between all input terminals and output terminals current cutoff 10 mA 2 0 kVAC for 1 min between all input terminals and PE terminals current cutoff 10 mA...

Page 3: ...2 0 kVAC for 1 min between all input terminals and PE terminals current cutoff 20 mA 1 0 kVAC for 1 min between all output terminals and PE terminals current cutoff 20 mA 500 VAC for 1 min between al...

Page 4: ...the above table 11 Refer to Recommended Replacement Periods and Periodic Replacement for Preventive Maintenance on page 23 for details 12 Refer to Standard Compliance below Standard Compliance EN IEC...

Page 5: ...othing circuit Overcurrent detection circuit AC L INPUT AC N S8VK S03024 30 W S8VK S06024 60 W V V V V V DC OUTPUT Voltage detection circuit Photocoupler Rectifier smoothing circuit Noise filter Drive...

Page 6: ...etection circuit Voltage detection circuit Overvoltage detection circuit Photocoupler S8VK S24024 240 W Overcurrent detection circuit V V V V V DC OUTPUT Rectifier smoothing circuit Smoothing circuit...

Page 7: ...1 Input terminals Connect the input lines to these terminals 1 2 L2 3 N1 4 N2 5 PE Protective Earth terminal PE Connect the ground line to this terminal 2 6 V1 DC Output terminals Connect the load lin...

Page 8: ...4 Horizontal separation 15 mm or more Note 1 At less than 90 VAC derate the load at 2 5 V 2 For a DC input reduce the load given in the above derating curve by multiplying by the following coefficient...

Page 9: ...e load at 1 V 2 For a DC input reduce the load given in the above derating curve by multiplying by the following coefficients S8VK S48024 0 8 3 In the shaded area time is required to reach the rated o...

Page 10: ...curve by multiplying by the following coefficients S8VK S12024 0 9 Standard mounting 30 60 W S8VK S03024 S8VK S06024 Front Side by side mounting Horizontal separation Less than 15 mm Note 1 Apply the...

Page 11: ...acket 240 W S8VK S24024 Front side by side mounting Horizontal separation Less than 15 mm Note 1 Apply the rated voltage Front Side by side mounting 480 W S8VK S48024 Front side by side mounting Horiz...

Page 12: ...ke below 1 The supplying voltage is below the maximum rated input OMRON Power supply allows the input voltage equivalent or less than 240 VAC 10 Please confirm the input voltage between two lines if t...

Page 13: ...mensions Unit mm Sliding 10 max Rail Stopper 1 2 90 1 86 3 5 5 4 78 55 4 7 90 1 5 4 32 1 S8VK S03024 30 W S8VK S06024 60 W 1 2 3 5 86 90 1 5 4 4 7 55 1 90 1 5 4 78 55 Sliding 10 max Rail Stopper S8VK...

Page 14: ...2 Sliding 8 0 max 5 4 5 7 8 38 1 108 8 19 8 20 4 124 1 122 2 1 117 8 111 4 5 4 S8VK S24024 240 W 10 8 1 2 1 4 0 6 0 6 7 5 5 4 5 18 3 0 9 19 8 20 4 108 8 60 1 111 4 117 8 122 2 1 124 1 5 2 Sliding 8 0...

Page 15: ...at the Unit will be subject to vibration or shock use a steel DIN Rail Otherwise metallic filings may result from aluminum abrasion 4 5 15 25 25 10 10 1 000 500 25 25 15 5 35 0 3 7 3 0 15 27 0 15 1 Va...

Page 16: ...Dimensions Appearance Front mounting bracket For 30 W and 60 W models S82Y VS10F Side mounting bracket For 30 W and 60 W models S82Y VS10S Front mounting bracket For 240 W and 480 W models S82Y VK10F...

Page 17: ...or cuttings resulting from installation work to enter the Product WARNING Indicates a potentially hazardous situation which if not avoided will result in minor or moderate injury or may result in seri...

Page 18: ...ck in direction B To dismount the Block pull down portion C with a flat blade screwdriver and pull out the Block Wiring Connect the ground completely A protective earthing terminal stipulated in safet...

Page 19: ...he angle should be between 10 and 15 If the flat blade screwdriver is inserted correctly you will feel the spring in the release hole 2 With the flat blade screwdriver still inserted into the release...

Page 20: ...iorate or be damaged if a short circuited or overcurrent state continues during operation Internal parts may possibly deteriorate or be damaged if the Power Supply is used for applications with freque...

Page 21: ...Supplies can be connected in parallel You must meet the following conditions to use parallel operation Standard mounting The range of ambient temperature is 25 to 40 C Left and right interval 15 mm o...

Page 22: ...rge occurs while turning ON the power supply In case there is no output voltage please check the following points before contacting us Checking overload protected status Check whether the load is in o...

Page 23: ...re used in the Power Supply and the Power Supply depends on the correct operation of these components to achieve the original Power Supply functions and performance However the influence of the ambien...

Page 24: ...MEMO 24...

Page 25: ...25 MEMO...

Page 26: ...MEMO 26...