6. Maintenance and inspection
2-4
Hold down the snap-on plug of the battery connecting cable
q
, and pull the cable
w
. Hold the white
pullout label and remove the battery pack
e
, and pull out the battery pack toward you.
When you see a red tape stuck on the top
of the battery pack, you can demount the
battery by pulling out the pack 10cm
further. Hold the battery securely with your
both hands not to drop it.
Demount another battery pack in the same
way. Do not try to demount two battery packs
together. Doing so may cause dropping the
battery packs and injury as the center of
gravity of the battery packs leans toward the
front.
2-5
Insert a new battery pack into where you can hook the battery pack plug-in cable and the UPS connector
q
.
Insert the battery connecting cable plug into the connector of the UPS until it snaps on.
A fire may occur but it does not indicate failure.
•
Battery pack for replacement
Type: BP100XR
2-6
Insert a new battery into the UPS as far as it will go
q
. Secure clockwise the screw at the right upper
side of the battery pack
w
. Hook and insert another battery pack in the same way.
q
w
q
w