9. EChanging the setting of the functions

Remedies

The AC Input Plug is not put in a wall outlet.

Check whether the AC Input Plug is certainly put in a wall outlet.
The red button pops up from the AC Input Overcurrent Protection. (BU100XR2)
The AC Input Overcurrent Protection is OFF. (BU200XR2)

It is suspected that too many devices are connected to the UPS, or the devices
developed a short circuit. Reduce connected devices or check the fuses of
devices.
In a case where the devices connected to the UPS are normal, then disconnect all
of the devices from the UPS, turn on the Red button of the AC Input Overcurrent
protection and put the AC Input Plug in a wall outlet (commercial power). In case
that the AC Input Overcurrent Protection still remains OFF, you may assume a fail-
ure.

It is suspected that the battery is not changed fully.

Turn off every device linked to the UPS and charge the UPS for at least 8 hours.
After the completion of the battery charge, bring the UPS and every device linked
to the UPS to a standstill, and turn on the Start switch again.
Remove the ACA Input Plug from a wall outlet (commercial power).
In case where the battery mode does not function at all, replace the battery pack
as the life of the battery expired.

Voltage fluctuations at low voltage level occur frequently or the voltage contains
noises, which bring about an extreme distortion of the voltage waveform.

Change the wall outlet (commercial power) to which you put the plug of the UPS.
Plug the UPS in other wall outlet (commercial power) at some distance away from
the devices that consumes large power.

The similar problem may occur also when you put many devices in a plug strip or
extension cord plugged in the UPS as well.

It is assumed that a noise occurred inside of the UPS causes jitter and white lines of
the display.

Ground the UPS and every device linked to the UPS. Put them in a grounding-type
receptacle (commercial power), or a receptacle with a grounding terminal.

The problems may occur where a power cord is too long, some of the power cords
are adjacent to one another, or the UPS and devices to linked to the UPS are adja-
cent one another. Change the placement of the UPS and devices

If the UPS or devices connected to the UPS are placed in a metal rack, ground the
rack.

The total capacity of the devices connected to the Power Supply Output Recep-
tacles of the UPS exceeds the rated capacity; 1 KVA/700W for BU100XR2 or 2KVA/
1.4KW for BU200XR2.

Reduce connected devices.

The auto battery test indicated that the life of the battery expired.

The battery mode cannot be functioned and therefore replace the battery pack.

An error or faulty has occurred in the UPS.

Bring the UPS and the devices connected to the UPS to a standstill.
Remove every device connected to the UPS, and then turn on the Start switch of
the UPS. In the case the UPS restores in usual service condition, it is assumed that
the some of the devices linked to the UPS developed a short circuit. Check de-
vices.
In the case where the problem still persists, bring the UPS to a standstill for one
hour, and then restart the UPS. In a case where the UPS restores in usual service
condition, it is assumed temperature rise, then improve ventilation around the UPS.
Finally if you cannot solve the problem after one hour, it is assumed that the UPS
may be out of order and need repair.
Contact us:

It is assumed that output fuse is burnt.

Stop operation of UPS and check the output fuse.
Replace the fuse if it is burnt.

10. Troubleshooting

Problems

The UPS does not operate, or the
AC Input Lamp does not go on.

Battery mode does not function.
The devices connected the UPS
comes to a stop when a power
failure occurs.

The UPS enters into the battery
mode frequently

The display of devices linked to
the UPS is abnormal.

Jitter of the display

While lines of the display

The Connection Capacity
Exceeded Lamp goes on.

The Battery Replacement Lamp
goes on.

The Error Lamp goes on.

No output despite operation
mode indication is normal
(For BU200XR2 only)

Summary of Contents for POWLI BU100XR2

Page 1: ...evices Keep this instruction manual within easy reach where you will install BU100XR2 BU200XR2 so that you can read it whenever necessary No part or whole of this manual may be reproduced without perm...

Page 2: ...personal computers Do not use the UPS with the devices that require very high reliability and safety as listed below Medical devices that may cause death directly Particular applications of devices t...

Page 3: ...es 2 SYMBOL This symbol indicates earth ground This symbol indicates turining on UPS This symbol indicates turining off UPS 3 INTERNAL BATTERY Internal battery voltage is 36Vdc for BU100XR2 72Vdc for...

Page 4: ...uring method of the backup time 32 5 2 Estimated backup time 32 6 Maintenance and inspection 33 6 1 Checking the battery 33 6 2 Replacing the battery 33 6 3 Cleaning 40 6 4 Cautions at the maintenance...

Page 5: ...inside of the battery Unpack and carry out the UPS bearing the weight in mind Place and run the UPS on a structurally sound base Toppling and dropping may cause injury The weight of the UPS BU100XR2 1...

Page 6: ...inlets and outlets on the upper and rear sides of the UPS Do not place the UPS in an enclosed space or put a cover the UPS Doing so may lead to an abnormal overheat or fire Temperature will increase...

Page 7: ...you notice abnormal sound or smell smoke or liquid from the inside of the UPS press the Stop switch of the UPS immediately and remove the AC Input Plug from a wall outlet commercial power A continuou...

Page 8: ...ll outlet commercial power the UPS starts feeding power at the starting time of the scheduled operation Cautions maintenance Do not short the battery with a metal thing Doing so may cause a burn or fi...

Page 9: ...s well as a ground fault between the output lines and the ground The UPS may fail Do not put the AC Input Plug of the UPS in the Power Supply Output Receptacle of the UPS The UPS may fail Turn off the...

Page 10: ...months the internal timer will be reset and the scheduled operating mode will not work Notice that a shutdown should reduce to approximately half where the battery is dead In a case where a shutdown e...

Page 11: ...ing software Attached to the BU100XR2 BU200XR2 1 Instruction Manual 1 2 Installation CD ROM 1 3 Connecting cable 9 pin serial cable 1 4 User registration card 1 Care must be taken on unpacking of BU10...

Page 12: ...t Connector Power Supply Output Receptacles Backup is carried in the event of a power failure Air Outlet Power Supply Output Receptacles Backup is carried in the event of a power failure RS232C signal...

Page 13: ...ly 1 4 Explanetion of symbol used on unit Symbol Description Start the UPS Stop the UPS Suspend a beep Expanding battery unit connecting to the UPS For BU100XS only UPS has Error Connected Overload Ex...

Page 14: ...adaptor for an AC Input Plug be sure to perform grounding before putting the AC Input Plug in a wall outlet commercial power On the other hand be sure to perform disconnecting a grounding terminal af...

Page 15: ...Do not obstruct the air inlets and outlets on the upper and rear sides of the UPS Do not place the UPS in an enclosed space or put a cover the UPS Doing so may lead to an abnormal overheat or fire Te...

Page 16: ...on both sides of the UPS with 6 screws M4 X 6mm steel countersunk screws 2 Unscrew the rubber seats counterclockwise installed in the four corners of the underside and remove them all 3 The installat...

Page 17: ...ion When connecting the battery and or adding another battery be sure to place the battery below Horizontal position 2 Stationary installation The UPS permits the following positions shown in the illu...

Page 18: ...lock The wire size based on the ampacities given in the National Electrical Code ANSI NFPA 70 1993 and the derating factor described in Underwriters Laboratories Inc Standerd for Safety UL1778 1994 AC...

Page 19: ...e VA is described as A ampere perform mathematical calculations A X 100 ___VA In the event that resultant total volt ampere exceeds 1500VA change the AC Input Cable Explanation When reconnect AC Input...

Page 20: ...the Battery Add on Connector of BU100XR2 and the Battery Connector of the battery unit After putting an AC Input plug in a Connection lamp on the front panel of the battery unit will light up BU100XR...

Page 21: ...device you want to put is 2 pin type you can plug it directly in the Power Supply Output Receptacle of the UPS however in a case of the input plug is 2 pin type with the attached grounding wire conne...

Page 22: ...ualified electrician Type II or higher and instruct him or her to replace the plug of the device 3 Connect between the UPS and the surge protection circuit See 7 Using the Network Line Surge Protectio...

Page 23: ...he metal part of the input plug Prior to use of the UPS follow the steps below to check whether backup function works This operational check of removing the AC Input Plug from the wall outlet is carri...

Page 24: ...urs in devices of 3 4 Beep sound and how to look at the display on page 28 take necessary measures according to the troubleshooting and then go back to 4 In a case where there is no backup and both th...

Page 25: ...shipment however the backup time may be shorter when using the UPS for the first time due to spontaneous discharge We recommend to charge the UPS before using it 2 10 Measuring the backup time After...

Page 26: ...let commercial power Even if you remove the AC Input Plug during the operation of the UPS the backup function of the UPS keeps feeding power through the power supply output receptacle of the UPS In a...

Page 27: ...use a failure or malfunction of the battery Notes Before cutting out commercial power by turning off the breaker or disconnecting the AC Input Plug stop the UPS If you cannot turn off the UPS it is re...

Page 28: ...on and supplying power from the Power Supply Output Receptacle of the UPS starts The Battery indicator lamp goes on and Level Meter displays the power consumption in percent of the devices linked to t...

Page 29: ...ks Remedy Put the AC Input Plug 1 2 None None Stop Stop Stop ON The AC Input Plug is put and the input power supply is normal Operation is stopped Remedy None No Display Beep Output Charge Description...

Page 30: ...top ON or stop No Display Beep Output Charge Description AC 15A B Failure display and beep when a power failure and or irregularities in the mains supply occurs Continuous Every 4 seconds ON Stop dis...

Page 31: ...ery to be charged fully 3 Continuous ON ON No Display Beep Output Charge Description 2 Continuous ON ON Status The rated output capacity is exceeded due toThe rated output capacity is exceeded due to...

Page 32: ...he UPS is necessary and or whether the internal circuit is at fault 1 Connect your PC and other devices to the UPS and then press the Start switch to get your UPS running 2 Press and hold the Start sw...

Page 33: ...tware The factory shipped setting is Enable the auto battery test 1 When the auto battery test starts your UPS enters automatically into the battery mode No beep sounds After the completion of the bat...

Page 34: ...e The backup time varies depending on the capacity of devices connected to the UPS After calculating the total capacity of devices connected to the UPS refer to the graph of the backup time to obtain...

Page 35: ...ending on storage conditions the surroundings and backup frequency As the battery life draws near the deterioration takes place much faster Check the battery regularly by yourself 1 Battery life repla...

Page 36: ...e gas A spark may occur when connecting the battery and lead to a fire Replace a battery on a structurally sound base Hold the battery securely with your both hands to avoid dropping Not doing so may...

Page 37: ...t panel was removed q Holding down the snap on plug of the battery connecting cable w pull the battery able toward you e 1 4 Hold the white pullout label at the bottom of the battery pack and graduall...

Page 38: ...the replacement date on the label at the top of the UPS In a case where you use the UPS monitoring software input the replacement date of the new battery After the replacement of the battery press th...

Page 39: ...same way hold the handgrip of the right front panel and slide the right panel to the right e and pull it toward you r While holding snap on cable connector attached to the panel pull out the cable con...

Page 40: ...ot try to demount two battery packs together Doing so may cause dropping the battery packs and injury as the center of gravity of the battery packs leans toward the front 2 5 Insert a new battery pack...

Page 41: ...software input the replacement date of the new battery After the replacement of the battery press the Start switch for over 20 seconds and carry out the self diagnostic test at the time of replacemen...

Page 42: ...the UPS starts feeding power at the starting time of the scheduled operation 6 3 Cleaning 1 Cleaning of the UPS Damp a soft cloth with water or detergent squeezes it tightly and wipes the UPS lightly...

Page 43: ...J11 2 pins 4 pins or 6 pins 7 1 When connecting to the telephone line or ISDN line Connect the telephone line that comes out of the wall to the Line Hub Side of the Network Line Surge Protection of th...

Page 44: ...Modem TA LAN Modem TA LAN Telephone line ISDN line or 10Base T 100Base Tx Telephone line ISDN line or 10Base T 100Base Tx Connect to the Modem TA PC Side Connect to the Line Hub Side Connect to the M...

Page 45: ...to shut off commercial power at the same time you must set the starting time shorter than 90 days after the commencement of this scheduled operating mode If you make the settings of the scheduled oper...

Page 46: ...tting such as Restore On AC Power Loss at the BIOS settings and change to a Startup power returned system setting such as Power On Individual BIOS setting method and or display may differ depending on...

Page 47: ...Details on Contact Signal I O You can develop your unique system based on the following specifications to automate the process at a power failure You can perform power failure processing by allowing t...

Page 48: ...can be set change from the UPS on page 47 5 Contact Signal I O circuit inside the UPS 6 Example of the use of the Contact Signal I O circuit 8 6 Precautions and notes on the use of the Contact Signal...

Page 49: ...les you to perform auto save processing the contact signal that enables you to configure a shutdown system and others change the settings of Accept both during line mode and during battery mode In a c...

Page 50: ...ted 9 2 Functions that can be set change from the UPS monitoring software 1 Beeper ON OFF setting ON The beeper sounds when an alarm is necessary OFF Let the beeper disable Factory setting ON 2 Auto b...

Page 51: ...cle commercial power or a receptacle with a grounding terminal The problems may occur where a power cord is too long some of the power cords are adjacent to one another or the UPS and devices to linke...

Page 52: ...lue 20 C Rated load 80 for 4 hours 500VDC BU100XR2 BU200XR2 BU100XR2 BU200XR2 main unit MB1002 MB200XR2 Battery unit BU100XR2 BU200XR2 main unit MB1002 MB200XR2 Battery unit Full time inverter power s...

Page 53: ...nsional outline drawings 440 445 88 Lubber seat height 18mm BU100XR2 BU200XR2 main unit Rackmount fittings MB100XR2 MB200XR2 Battery unit 88 440 5 0 440 88 445 426 440 88 445 3 0 52 0 19 0 25 0 21 3 1...

Page 54: ...eral devices C Circuit block diagram 100 VAC input Input overcurrent protection Noise filter Power supply relay Charging circuit Rectifier high power factor conversion Step up converter Battery Commer...

Page 55: ...BU100 200XR2 B No part or whole of this manual may be reproduced without permission The contents of this manual are subject to change without notice OMRON Corporation...

Reviews: