14
2. Installation and connection
2-2 Installation
The UPS permits the following installing methods according to its surroundings.
1. Rackmount installation
2. Stationary installation
1. Rackmount installation (JIS/EIA 19-inch rack/sever rack)
Cautions
In a case where the UPS is to be mounted on a rack, place it on the
lowest part of the rack.
●
Dropping may cause injury.
●
The weight of the UPS
BU100XR2: 19kg
MB100XR2: 26kg (add-on battery unit)
BU200XR2: 12kg (main unit)
MB200XR2: 26kg (battery unit)
Do not install the UPS alone but ask your colleagues for help.
●
Dropping may cause injury.
(1) Mount supplied 19-inch rackmount fittings on both sides
of the UPS with 6 screws (M4 X 6mm steel countersunk
screws).
(2) Unscrew the rubber seats counterclockwise installed in
the four corners of the underside and remove them all.
(3)
•
The installation of the UPS on 19-inch rack.
a. Remove the supplied rackmount screws (M5 X 15cm
steel pan head screws).
b. Screw the UPS to the rack keeping it in a horizontal
position. Exercise care to avoid creating clearance
between the fittings and rack.
•
The installation of the UPS on a server rack
a. Remove the secured rackmount screws (M5 X 15cm
steel pan head screws).
b. Install rackmount nut on the rack.
c. Screw the UPS to the rack keeping it in a horizontal
position. Exercise care to avoid creating clearance
between the fittings and rack.
In a case where the UPS is to be mounted on a rack, place it on the
lowest part of the rack.