8. Using SNMP/WEb card
8. Using SNMP/Web card
8-1 Addition of SNMP/Web card
An SNMP/Web card can be loaded in the option card slot on the backside of the UPS.
•
SNMP/Web cards (Model: SC20) are sold separately.
8-2 SNMP/Web card outline
●
Description (features)
•
SNMP management of the UPS through the network is possible. Supports UPS MIB.
•
Has a function that links one UPS to another. Even in cases such as when a separate UPS is used for each
the server and storage, it is possible for the two UPSs to work together to carry out shutdown operation.
•
No serial connector; use of blade server is possible.
•
Setting functions: Possible to make settings by using browser, telnet, or serial connection.
•
Log functions: Data log, event log, syslog, and mail notification are possible.
•
Security functions: Access is controlled by ID, password, and IP address at time of HTTP and SNMP
access.
•
UPS monitor function: Monitoring of UPS status, such as input/output voltage, battery status, and connec-
tion load, is possible.
•
UPS control function: With the included UPS monitoring software, shutdown is possible when there is a
power supply failure.
Possible to perform scheduled shutdown or startup immediately via the network.
•
Network function: Possible to change port numbers for SNMP, HTTP, and telnet.
●
Specifications
LAN port
10/100 Mb
Network protocol
SNMP, HTTP, ARPR, TFTP, ICMP
Other communication route
Serial connection asynchronous system (setting only)
Number of controllable computers Maximum of 32 (this includes slave UPS when coordinated
shutdown is in effect)
Support MIB
UPSMIB (RFC1628), OMRON MIB
Other
Equipped with real-time lock
UPS monitoring software-
Windows NT 4.0, Windows 2000, Windows XP, Widows Server 2003
compatible OS
Red Hat Linux 7.27/7.3/8.0
Red Hat Enterprise Linux AS/ES/WS (Red Hat Linux Advanced
Server 2.1)
Note: Limited to IA32 environment.