3. Operating the UPS
Status:
Battery replacement is necessary.
Remedy:
●
Charge the battery for at least 12 hours. (For
information on how to charge the battery,
refer to "2-7 Charging the battery" on page
29.) After charging is complete, check
whether Battery mode performs according
to "2-6 Checking the operation" on page 28.
In a case where the UPS performs no backup
or the backup time became less than half of
the initial value, the battery, which is in a
deteriorated condition, needs replacing.
(For information on the procedure to replace
the battery, refer to "5-2 Replacing the
battery" on page 37.)
●
The display will be turned off either by turning
OFF the power switch, or by performing a
self-diagnosis test on the battery after
replacing it.
●
The battery deterioration indicator can be
turned off without stopping the output if the
power switch is turned back ON within 3
seconds of being turned OFF.
●
If you continue to use a weak battery, and
there is a power failure, the Battery mode
will not work and output will stop.
3
Every 2
seconds
ON
ON
No.
Display
Beep
Output Charge
Description
2
Every 0.5
second
ON
ON
Status:
The rated output capacity is exceeded
because too many devices are linked to the
UPS. When this status continues for the
periods of time shown below, it will become
the C-1 status above.
Amount of the current capacity 110% or
more: 5 minutes
Amount of the current capacity 120% or
more: 30 seconds
Amount of the current capacity 115% or
more: 10 seconds (Backup)
Amount of the current capacity 125% or
more: fraction of a second (Backup)
Remedy:
Reduce the number of devices linked to the
UPS until the above display turns off and
shows the display as in A-3 on page 33.
AC115V
OUTPUT
B
25% 50% 75% 100%
C
Lit
Blinking
Not lit
Blinking
Lit or not lit,
depending on status
AC115V
OUTPUT
B
25% 50% 75% 100%
C
Blinks once every 2 seconds
Lit
Not lit
Blinking
Lit or not lit,
depending on status
4
Con-
tinuous
None Stopped Status:
Circuit failure
Power switch : OFF
Remedy:
●
There is trouble with the circuit.
The alarm stops when commercial power is
cut, or when the AC plug is unplugged.
Contact the dealer or our Electronic Systems
& Equipments repair center.