2. Installation and connection
2-2 Installation
The UPS permits the following installing methods. Choose the one best suited for the environment.
1. Rackmount installation
2. Stationary installation
●
Horizontal
●
Upright intatllation for BN240XR/MB240XR
1. Rackmount installation (EIA 19-inch rack/server rack)
Cautions
When performing rack installation, ensure that the UPS is supported and
stabilized by using both the support angles and the table clamps that were
included.
When connecting a battery unit and/or adding another battery unit, be sure
to place the battery unit in a position lower than the main unit.
●
When installing on a rack, make sure that the UPS is supported by the each unit individually.
●
When installing on a rack, make sure to use the support angles and table clamps included with
the product. Without the support angles, the front clamp alone cannot support the weight of the
UPS.
●
The mass of the UPS: BN100XR: 20 kg
BN150XR: 20 kg
BN240XR: 38 kg
MB240XR: 29 kg (add-on battery unit)
In a case where the UPS is to be mounted on a rack, place it on the lowest
part of the rack.
●
Dropping it may result in injury.
Be sure to use the supplied mounting screws.
●
Screws other than those supplied may not be strong enough to support the UPS, causing it to fall.
●
Rack installation for BN100XR/BN150XR
Follow steps
1
through
6
for installation.
Make sure to use the support clamps (support angles, front support clamp