24
2. Installation and connection
2-4 Connection of AC input cable
1. BN100XR
•
It is possible to use a wall outlet (commercial power) with a basic 15A pin (NEMA 5-15).
•
It is possible to connect to a 2-pin outlet using the included 3-pin to 2-pin adapter.
In this case, make sure that the grounding is connected separately.
2. BN150XR
●
A 15A plug (NEMA 5-15) is included with the BN150XR at shipment. If this plug is used, make sure that
the capacity of the connected devices stays below the maximum capacities shown in the table below.
●
If the "Input over 15A" indication (
symbol blinks every 0.5 second) appears, do not continue to use
a 15A plug.
Replace it with the 20A plug that was included.
●
Use of 15A plug
•
It is possible to use a wall outlet (commercial power) with a basic 15A pin (NEMA 5-15).
•
It is possible to connect to a 2-pin outlet using the included 3-pin to 2-pin adapter.
In this case, make sure that the grounding is connected separately.
Caution
When using the 15A plug (NEMA 5-15P)
The maximum capacity that can be connected to the output is about 1100VA/1000W.
•
Power consumption over that exceeds the values indicated in the table below results in an input
current of more than 15A, which can lead to overheating or fire.
•
When the "Input over 15A" display appears, replace it with a 20A plug.
•
When the AC input is connected directly from a power switchboard, make sure that the wiring work is
performed by a qualified electrical engineer (with Type II certification or higher).
Wiring capacity of 20A or more is required. (Recommended cable: nominal cross-section of 3.5mm
2
(AWG12) or more)
Maximum capacity that can be connected when using 15A plug
Voltage setting mode
Maximum output capacity
100V AC output/normal voltage sensitivity
1110VA/1000W
100V AC output/low voltage sensitivity
1035VA/1000W
115V AC output/normal voltage sensitivity
1140VA/1000W
115V AC output/low voltage sensitivity
1080VA/1000W