Parallel Wiring (Single Phase)
Correct
Correct
Power supply
Incorrect
Power supply
Power supply
Load
Load
Load
Conduits
Conduits
Conduits
NG
OK
OK
• Power cables and signal cables adversely affect each other. Do not wire them in parallel.
• Noise induction may occur if the Panel PC is installed in a panel that includes high-voltage devi-
ces. Wire and install them as far apart as possible.
• Either install the Panel PC a minimum of 200 mm away from high-voltage lines or power lines, or
place the high-voltage lines or power lines in metal tubing and completely ground the metal tub-
ing to 100 Ω or less.
Example: Separating an OMRON product from Power Lines
Metal tubing
200 mm
200 mm
High-voltage power panel
Power lines
Power lines
Ground of
100 Ω or less
OMRON
product
OMRON
product
Wiring Ducts
Whenever possible, route the cables and wires through wiring ducts.
Install the wiring ducts so that it is easy to route the wires from the Industrial Panel PC directly into
the duct.
Additional Information
Refer to
on page 5-16 for the minimum required distances.
It is convenient to use wiring ducts that have the same depth as the Industrial Panel PC.
Duct
Product
5 Installation
5-23
NY-series Industrial Panel PC Hardware User's Manual (W555)
5-3 Mount
5
5-3-7
Electrical Environment
Summary of Contents for NYP - 1 Series
Page 4: ...Introduction 2 NY series Industrial Panel PC Hardware User s Manual W555...
Page 10: ...Index CONTENTS 8 NY series Industrial Panel PC Hardware User s Manual W555...
Page 44: ...1 Overview 1 10 NY series Industrial Panel PC Hardware User s Manual W555...
Page 261: ...I Index I 1 NY series Industrial Panel PC Hardware User s Manual W555 I...
Page 264: ...Index I 4 NY series Industrial Panel PC Hardware User s Manual W555...
Page 265: ......