Power Connector Wiring Materials
Use the power supply connector that was supplied to connect the power supply to the Industrial Panel
PC.
• Select power supply conductors with consideration to the voltage drop and heat generation for the
cable length at the installation environment.
• Always use twisted wires to minimize the occurrence of electrical disturbance.
• Recommended power supply conductor sizes are provided in the table.
Wire type
Conductor cross-section
Solid conductor
0.5 to 10 mm
2
Flexible conductor
0.5 to 6 mm
2
Flexible conductor, with ferrule and no plastic sleeve
0.5 to 6 mm
2
Flexible conductor, with ferrule and plastic sleeve
0.5 to 4 mm
2
Minimum AWG according to UL/cUL
20
Maximum AWG according to UL/cUL
8
• Power Supply Connector
DC Power Supply
The OMRON S8VK-series power supply is recommended for use with the Industrial Panel PC.
Additional Information
• Refer to
on page 3-31 for more information.
• Refer to
4-1-3 Power Consumption Specifications
on page 4-6 for power consumption details.
5 Installation
5-36
NY-series Industrial Panel PC Hardware User's Manual (W555)