5-3-3
Temperature
The temperature inside a control panel may be at least 10 to 15°C higher than outside the panel. Im-
plement the following measures against overheating at the installation site and in the control panel,
and allow a sufficient margin for the temperature.
Distance for Cooling
Adequate airflow around the Industrial Panel PC is required.
Additional Information
• The ambient temperature must be within the operating range.
Refer to
4-4-1 Operation Environment Specifications
on page 4-34 for temperature specifica-
tions.
• Allow space to accommodate for the bending radius of the cables.
Refer to:
•
•
3-10-6 USB Type-A to USB Type-B Cables
•
• individual cable specifications
for cable bending requirements and connector clearance.
Provide enough space for good air flow and ensure the following minimum distances are observed
around the sides of the Industrial Panel PC for landscape
A
and portrait
B
orientations.
X
X
Z
X
X
Y
Y
Y
Y
A
B
B
+
A
Item
Minimum distance
X
50 mm
Y
100 mm
Z
50 mm
5 Installation
5-16
NY-series Industrial Panel PC Hardware User's Manual (W555)