101
6
. Detailed settings for communications
6.4 Address map (continued)
address
Type
Parameter name
Setting (monitor) value
R/W
Modbus
CompoWay/F
220E
1107
Common
settings
VT ratio
H'00000064 to H'0001869F
(100 to 99999)
100 times the VT ratio
R/W
2210
1108
Conversion factor
H'00000000 to H'0001869F
(0 to 99999)
1000 times the factor
R/W
2212
1109
Conversion units (characters)
Characters in hexadecimal display of 3 characters
worth of ASCII code
R/W
2214
110A
Automatic LCD off time
H’00000000:OFF
H’00000001:1 minute
H’00000002:5 minutes
H’00000003:10 minutes
R/W
2218
110C
Alarm ON/OFF
H’00000000:OFF
H’00000001:ON
R/W
221A
110D
Tariff ON/OFF
H’00000000:OFF
H’00000001:ON
R/W
221C
110E
Current tariff
H'00000000:T1
H'00000001:T2
H'00000002:T3
H'00000003:T4
R/W
2400
1200
Model 1 (KM-N)
The model is shown in ASCII code, with the first 1
to 4 characters starting on the left when the
display is 12 characters aligned to the left.
R
2402
1201
Model 2 (2-FL)
The model is shown in ASCII code, with
characters 5 to 8 starting on the left when the
display is 12 characters aligned to the left.
R
2404
1202
Model 3 (K (sp)(sp)(sp))
The model is shown in ASCII code, with
characters 9 to 12 starting on the left when the
display is 12 characters aligned to the left.
(sp) indicates a space
R
2406
1203
Software version
For example: H’00000100
→
Ver1.0.0
R
2408
1204
Status information
Refer "Controller status read (0601)"
R
240A
1205
Buffer size
H'000000E6
(230 fixed)
R