. Detailed settings for communications
6.4 Address map
●
List of variable areas (measurement values)
Used when remotely controlling the unit.
address
Item
R/W
Modbus
CompoWay/F
Parameter name
Monitor value
0000
0000
Voltage 1 (V)
H'00000000 to H'0098967F
(0 to 9999999)
10 times the voltage
R
0002
0001
Voltage 2 (V)
R
0004
0002
Voltage 3 (V)
R
0006
0003
Current 1 (A)
H’00000000 to H’05F5E0FF
(0 to 99999999)
1000 times the current
R
0008
0004
Current 2 (A)
R
000A
0005
Current 3 (A)
R
000C
0006
Power factor
H’FFFFFF9C to H’00000064
(-100 to 100)
100 times the power factor
R
000E
0007
Frequency (Hz)
H’000001C2 to H’0000028A
(450 to 650)
10 times the frequency
R
0010
0008
Active power (W)
H’80000000 to H’7FFFFFFF
(-214748368 to 2147483647)
10 times the active and reactive power
R
0012
0009
Reactive power (Var)
R
0014
000A
Voltage V1-V2 (V)
H'00000000 to H'0098967F
(0 to 9999999)
10 times the voltage
R
0016
000B
Voltage V1-V3 (V)
R
0018
000C
Voltage V2-V3 (V)
R
0200
0100
Active energy (import) (not resettable) (Wh)
H'00000000 to H'3B9AC9FF
(0 to 999999999)
Value that is 1 times each value
R
0202
0101
Active energy (export) (not resettable) (Wh)
R
0204
0102
Reactive energy (import) (not resettable) (Varh)
R
0206
0103
Reactive energy (export) (not resettable) (Varh)
R
0208
0104
Cumulative total reactive power (not resettable)
(Varh)
R
020A
0105
T1 Active energy (import) (not resettable) (Wh)
R
020C
0106
T2 Active energy (import) (not resettable) (Wh)
R
020E
0107
T3 Active energy (import) (not resettable) (Wh)
R
0210
0108
T4 Active energy (import) (not resettable) (Wh)
R
0220
0110
Active energy (import) (not resettable) (kWh)
R
0222
0111
Active energy (export) (not resettable) (kWh)
R
0224
0112
Reactive energy (import) (not resettable) (kVarh)
R
0226
0113
Reactive energy (export) (not resettable) (kVarh)
R