100
6
. Detailed settings for communications
6.4 Address map (continued)
●
Parameter area list
Address
Type
Parameter name
Setting (monitor) value
R/W
Modbus
CompoWay/F
2000
1000
Unit
Individual
setting
Phase and wire type
H'00000000:1P2W
H'00000001:1P3W
H'00000002:3P3W
H'00000003:1P2W2
H'00000004:1P3W2
H'00000005:3P4W
R/W
2002
1001
Communication address
H'00000001 to H'00000063
(1 to 99): Modbus
H'00000000 to H'00000063
(0 to 99): when CompoWay/F
R
2010
1008
Pulse output ON/OFF
H’00000000:OFF
H’00000001:ON
R/W
2012
1009
Voltage selected
H'00000000:V_R
H'00000001:V_T
H'00000002:V_R-T
R/W
2014
100A
CT secondary side current
H’00000000:1A
H’00000001:5A
R/W
2016
100B
CT primary side current
H'00000000 to H'0001869F
(0 to 99999)
1 times the current
R/W
2200
1100
Common
settings
Protocol
H’00000000:CompoWay/F
H’00000001:Modbus
R/W
2202
1101
Communication speed
H'00000000:1200bps
H'00000001:2400bps
H'00000002:4800bps
H'00000003:9600bps
H'00000004:19200bps
H'00000005:38400bps
R/W
2204
1102
Data length
H’00000000:7bit
H’00000001:8bit
R/W
2206
1103
Stop bit
H’00000000:1bit
H’00000001:2bit
R/W
2208
1104
Parity
H’00000000:NONE
H’00000001:ODD
H’00000002:EVEN
R/W
220A
1105
Transmission wait time
H’00000000 to H’00000063
(0 to 99)
Wait time in msec units
R/W
220C
1106
Pulse output units
H'00000000:1Wh
H'00000001:10Wh
H'00000002:100Wh
H'00000003:1kWh
H'00000004:5kWh
H'00000005:10kWh
H'00000006:50kWh
H'00000007:100kWh
R/W