51
3.
Basic use
3.4 How to read the setting values (continued)
■
Setting item list
* The communication address can only be set using the rotary switch. You cannot set it with the [
] and [
] keys.
Cate-
gory
MENU
No.
Setting Item
Main display
Display of options and input values
Sub display
Unit
Default
Value
Remarks
Cir
cuit
A
A1
Phase and wire type
3P4W / 1P2W / 1P3W /
3P3W / 1P2W2 / 1P3W2
WIRE
3P4W
3P4W: 3-phase 4-wire, 1P2W: 1-phase 2-wire
1P3W: 1-phase 3-wire, 3P3W: 3-phase 3-wire
1P2W2: 1-phase 2-wire voltage selected
1P3W2: 1-phase 3-wire composite
A2
Communication address
*
Modbus : --, 01 to 99,
CompoWay/F : -- 00 to 99,
ADDRS
--
(invalid
value)
Set a different number for each circuit.
A3
CT secondary side current
1A / 5A
CT2ND
5A
Set to match the rating of the CT to be used.
A4
CT primary side current
1 to 99999
CT1ST
5
Rated values for the primary side of the CT to
be connected.
Set CT individually.
A5
Voltage assignment
V_R / V_T / V_R-T
V-SET
V_R
Set the voltage phase for 1-phase 2-wire
circuits when 1P2W2 is selected.
A6
Pulse output ON/OFF
ON / OFF
OUT
OFF
A7
Active energy reset
-----
0WH
-----
Clear the active energy for the circuit.
Cir
cuit
B
B0
Circuit B ON/OFF
ON / OFF
ACTIV
OFF
ON: Circuit enabled, measuring and setting possible.
OFF: Circuit disabled, measuring and setting not
possible.
B1
Phase and wire type
3P4W / 1P2W / 1P3W /
3P3W / 1P2W2 / 1P3W2
WIRE
--
Phase and wire type set in MENU No. A1
B2
Communication address
*
Modbus : --, 01 to 99,
CompoWay/F : -- 00 to 99,
ADDRS
--
(invalid
value)
Set a different number for each circuit.
B3
CT secondary side current
1A / 5A
CT2ND
5A
Set to match the rating of the CT to be used.
B4
CT primary side current
1 to 9999
CT1ST
5
Rated values for the primary side of the CT to
be connected.
Set CT individually.
B5
Voltage assignment
V_R / V_T / V_R-T
V-SET
V_R
Set the voltage phase for 1-phase 2-wire
circuits when 1P2W2 is selected.
B6
Pulse output ON/OFF
ON / OFF
OUT
OFF
B7
Active energy reset
-----
0WH
-----
Clear the active energy for the circuit.
Cir
cuit
C
C0
Circuit C ON/OFF
ON / OFF
ACTIV
OFF
ON: Circuit enabled, measuring and setting possible.
OFF: Circuit disabled, measuring and setting not
possible.
C1
Phase and wire type
3P4W / 1P2W / 1P3W /
3P3W / 1P2W2 / 1P3W2
WIRE
--
Phase and wire type set in MENU No. A1
C2
Communication address
*
Modbus : --, 01 to 99,
CompoWay/F : -- 00 to 99,
ADDRS
--
(invalid
value)
Set a different number for each circuit.
C3
CT secondary side current
1A / 5A
CT2ND
5A
Set to match the rating of the CT to be used.
C4
CT primary side current
1 to 99999
CT1ST
5
Set CT individually.
C5
Voltage assignment
V_R / V_T / V_R-T
V-SET
V_R
Set the voltage phase for 1-phase 2-wire
circuits when 1P2W2 or 1P3W2 is selected.
C6
Pulse output ON/OFF
ON / OFF
OUT
OFF
C7
Active energy reset
-----
0WH
-----
Clear the active energy for the circuit.
Cir
cuit
D
D0
Circuit D ON/OFF
ON / OFF
ACTIV
OFF
ON: Circuit enabled, measuring and setting possible.
OFF: Circuit disabled, measuring and setting not
possible.
D1
Phase and wire type
3P4W / 1P2W / 1P3W /
3P3W / 1P2W2 / 1P3W2
WIRE
--
Phase and wire type set in MENU No. A1
D2
Communication address
*
Modbus : --, 01 to 99,
CompoWay/F : -- 00 to 99,
ADDRS
--
(invalid
value)
Set a different number for each circuit.
D3
CT secondary side current
1A / 5A
CT2ND
5A
Set to match the rating of the CT to be used.
D4
CT primary side current
1 to 99999
CT1ST
5
Set CT individually.
D5
Voltage assignment
V_R / V_T / V_R-T
V-SET
V_R
Set the voltage phase for 1-phase 2-wire
circuits when 1P2W2 or 1P3W2 is selected.
D6
Pulse output ON/OFF
ON / OFF
OUT
OFF
D7
Active energy reset
-----
0WH
-----
Clear the active energy for the circuit.