background image

9

Safety Precautions

Be sure to read the precautions for all models in the website at the following URL: http://www.ia.omron.com/.

Warning Indications

Meaning of Product Safety Symbols

Electrical shock may cause minor injury.
Do not touch terminals while electricity is being supplied.

There is a risk of minor electrical shock, fire, or device failure. 

Do not allow any pieces of metal, conductors, or cutting chips 

that occur during the installation process to enter the product.

Explosions may cause minor injuries. Do not use the product  

in locations with inflammable or explosive gases.

There is a risk of minor electrical shock, fire, or device failure. 

Do not disassemble, modify, repair, or touch the inside of the 

product.

Loose screws may cause fires. Tighten terminal screws to the 

specified torque of 0.49 to 0.59 N·m.

Use of excessive torque may damage the terminal screws. 

Tighten terminal screws to the specified torque of 0.49 to 0.59 

N·m.

If the setting does not match the element to be monitored, the 

product may behave unexpectedly and damage the machine 

or cause accidents. Set the K8AK-TH as described below.

Adjust each set value on the K8AK-TH correctly for the 

element that is to be monitored.

Turn OFF the power to the K8AK-TH before you change 

the switch settings on the side panel. The switch 

settings made on the side panel take effect when the 

power is turned ON.

If the K8AK-TH fails, the monitoring alarms and alarm outputs 

may fail to operate. This may result in physical damage to the 

facilities, equipment, or other devices that are connected to it. 

To reduce this risk, inspect the product regularly. To make the 

product fail-safe, take alternative safety measures, such as the 

installation of monitoring devices on a separate circuit.

Use of the product beyond its life may result in contact welding 

or burning. Make sure to consider the actual operating 

conditions and use the product within its rated load and 

electrical life count. The life of the output relay varies 

significantly with the switching capacity and switching 

conditions.

1.

 Do not use or store the product in the following locations.

Locations subject to water or oil

Locations subject to direct radiant heat from heating equipment

Outdoor locations or under direct sunlight

Locations subject to dust or corrosive gases (particularly 

sulfurizing gases, ammonia, etc.)

Locations subject to rapid temperature changes

Locations prone to icing and dew condensation

Locations subject to excessive vibration or shock

Locations subject to wind and rain

Locations subject to static electricity and noise

Habitats of insects or small animals

2.

Use and store the product in a location where the ambient 

temperature and humidity are within the specified ranges. If 

applicable, provide forced cooling.

3.

Mount the product in the correct direction.

4.

Check terminal polarity when wiring and wire all connections 

correctly. The power supply terminals do not have polarity.

5.

Do not wire the input and output terminals incorrectly.

6.

Make sure the power supply voltage and loads are within the 

specifications and ratings for the product.

7.

Make sure the type of the thermocouple matches the input type 

that the K8AK-TH is designed for.

8.

If you need to extend the length of the lead wires on the 

thermocouple to use with the K8AK-TH, make sure to match the 

type of thermocouple and always use compensating conductors.

9.

To extend the lead wires on the platinum resistance thermometer 

that is used with the K8AK-TH, use lead wires with a low 

resistance (5 

Ω

 or less per wire), and make the resistance equal 

on all three lead wires.

10.

Make sure the crimp terminals for wiring are of the specified size.

11.

Do not connect anything to terminals that are not being used.

12.

Use a power supply that will reach the rated voltage within 1 

second after the power is turned ON.

13.

After you turn ON the power, it takes 2 seconds for the outputs of 

the K8AK-TH to stabilize. Take this time into account when you 

design the control panel.

14.

Allow at least 30 minutes for the K8AK-TH to warm up. During this 

time, the temperature measurements will be incorrect.

15.

Keep wiring separate from high voltages and power lines that 

draw large currents. 

Do not place product wiring in parallel with or in the same path as 

high-voltage or high-current lines.

16.

Do not install the product near equipment that generates high 

frequencies or surges.

17.

The product may cause incoming radio wave interference. Do not 

use the product near radio wave receivers.

18.

Install an external switch or circuit breaker and label it clearly so 

that the operator can quickly turn OFF the power supply.

 CAUTION

Indicates a potentially hazardous situation 

which, if not avoided, may result in minor or 

moderate injury or in property damage.

Precautions for Safe 

Use

Supplementary comments on what to do or 

avoid doing, to use the product safely.

Precautions for 

Correct Use

Supplementary comments on what to do or 

avoid doing, to prevent failure to operate, 

malfunction, or undesirable effects on 

product performance.

Used to warn of the risk of electric shock under 

specific conditions.

Used for general prohibitions for which there is no 

specific symbol.

Used to indicate prohibition when there is a risk of 

minor injury from electrical shock or other source if 

the product is disassembled.

Used for general mandatory action precautions for 

which there is no specified symbol.

 CAUTION

Precautions for Safe Use

Summary of Contents for K8AK-AS

Page 1: ...ble Accessory Order Separately OMRON CT Commercially Available CTs If you use a commercially available CT do notexceed the overload capacity of the K8AK AS2 Refer to Safety Precautions for the K8AK Se...

Page 2: ...K8AK AS2 0 1 to 1 A AC DC Compatible with commercially available CTs 0 5 to 5 A AC DC Compatible with commercially available CTs 0 8 to 8 A AC DC K8AK AS3 When used with the OMRON CT K8AC CT200L 10 t...

Page 3: ...humidity rated power supply voltage DC or 50 60 Hz sine wave input Operating time 50 ms at 25 C and 65 humidity rated power supply voltage Applicable standards Conforming standards EN60947 5 1 Install...

Page 4: ...5 and 10 mm min Test method Relationship of Mounting Distance between K8AK AS Relays and Input Current Reference Values The following diagram shows the relationship between the mounting distances and...

Page 5: ...e notes 1 and 2 Terminal block See notes 1 and 2 Item Meaning Power indicator PWR Green Lit when power is being supplied Relay status indicator RY Yellow Lit when relay is operating Alarm indicator AL...

Page 6: ...input terminal Example K8AK AS3 Using Input Terminals I3 COM The maximum setting range will be 200 A AC and the setting range will be 20 to 200 A 2 Hysteresis Hysteresis is set using the hysteresis k...

Page 7: ...lashes when the set value and the input have reached the same level Use this as a guide to set the startup lock time The startup lock time will start when the input current reaches 30 or more of the s...

Page 8: ...ure for information on the motor startup current For a motor with a rating of 5 A the startup current will be approximately 30 A The startup current will exceed the overload capacity rating 150 for 1...

Page 9: ...s 2 Use and store the product in a location where the ambient temperature and humidity are within the specified ranges If applicable provide forced cooling 3 Mount the product in the correct direction...

Page 10: ...will be large if the K8AK AS K8AK AW K8AK VS or K8AK VW is used for thyristor or inverter control The K8AK PH K8AK PA K8AK PM K8AK PW or K8DS PH cannot be used on the secondary side of an inverter To...

Page 11: ...nt or addition to the above warranty See http www omron247 com or contact your Omron representative for pub lished information 14 Limitation on Liability Etc OMRON COMPANIES SHALL NOT BE LIABLE FOR SP...

Page 12: ...rasil 55 11 2101 6300 www omron com br OMRON ARGENTINA SALES OFFICE Cono Sur 54 11 4783 5300 OMRON CHILE SALES OFFICE Santiago 56 9 9917 3920 OTHER OMRON LATIN AMERICA SALES 54 11 4783 5300 OMRON INDU...

Reviews: