K8AK-AS

2

Ratings and Specifications

Input Range

*1 The range is selected using connected terminals.

*2 The K8AK-AS3 is designed to be used in combination with an OMRON K8AC-CT200L Current Transformer (CT). (Direct input is not possible.)

Ratings

Model

Range

*1

Connection 

terminal

Setting range

Input impedance

Input type

Overload capacity

K8AK-AS1

0 to 20 mA AC/DC

I1-COM

2 to 20 mA AC/DC, 

10 to 100 mA AC/

DC, 50 to 500 mA 

AC/DC

Approx. 5 

Ω

Direct input

Continuous input at

120% of maximum input

1 s at 150%

0 to 100 mA AC/DC I2-COM

Approx. 1 

Ω

Direct input

0 to 500 mA AC/DC I3-COM

Approx. 0.2 

Ω

Direct input

K8AK-AS2

0 to 1 A AC/DC

I1-COM

0.1 to 1 A AC/DC, 

0.5 to 5 A AC/DC, 

0.8 to 8 A AC/DC

Approx. 0.12 

Ω 

(Load : 0.5 VA)

Direct input 

or commer-

cially avail-

able CT

0 to 5 A AC/DC

I2-COM

Approx. 0.02 

Ω

 

(Load : 1.5 VA)

0 to 8 A AC/DC

I3-COM

Approx. 0.02 

Ω

 

(Load : 3 VA)

---

K8AK-AS3

0 to 100 A AC

I2-COM

10 to 100 A AC

*2

20 to 200 A AC

*2

 

---

OMRON CT Continuous input at 120% with 

an OMRON CT (K8AC-

CT200L).

30 s at 200%

1 s at 600%

* CT capacity on primary side.

0 to 200 A AC

I3-COM

---

OMRON CT

Power supply voltage Isolated power supply

24 VAC/DC

100 to 240 VAC

Power consumption

24 VAC/DC: 2.0 VA/1.1 W max.

100 to 240 VAC: 4.6 VA max.

Operating value setting range (SV)

10% to 100% of the maximum value of the setting range

K8AK-AS1:  2 to 20 mA AC/DC

10 to 100 mA AC/DC

50 to 500 mA AC/DC

K8AK-AS2:  0.1 to 1 A AC/DC (Compatible with commercially available CTs.)

0.5 to 5 A AC/DC (Compatible with commercially available CTs.)

0.8 to 8 A AC/DC

K8AK-AS3:  When used with the OMRON CT (K8AC-CT200L).

10 to 100 A AC

20 to 200 A AC

Operating value

100% operation at set value

Reset value setting range (HYS.)

5% to 50% of operating value

Reset method

Manual reset/automatic reset (switchable)

Note:

Manual reset: Turn OFF power supply for 1 s or longer.

Operating time setting range (T)

0.1 to 30 s

Startup lock time setting range (LOCK)

Note:

Enabled only for overcurrent operation.

0 to 30 s

(The startup lock timer starts when the input has reached approximately 30% or more of the set value.)

Note:

Enabled only for overcurrent operation.

Indicators

Power (PWR): Green, Relay output (RY): Yellow, Alarm outputs (ALM): Red

Input impedance

Refer to 

Input Range

 on this page.

Output relays

One SPDT relay (NO/NC switched using DIP switch.)

Output relay ratings

Rated load

Resistive load

5 A at 250 VAC

5 A at 30 VDC

Maximum contact voltage: 250 VAC or 30 VDC

Max. switching current: 5 A

Maximum switching capacity: 1,250 VA, 150 W

Mechanical life: 10 million operations min.

Electrical life:  5 A at 250 VAC or 30 VDC: 50,000 operations

3 A at 250 VAC/30 VDC:100,000 operations

Ambient operating temperature

20 to 60°C (with no condensation or icing)

Storage temperature

25 to 65°C (with no condensation or icing)

Ambient operating humidity

25% to 85% (with no condensation)

Storage humidity

25% to 85% (with no condensation)

Altitude

2,000 m max.

Terminal screw tightening torque

0.49 N·m

Summary of Contents for K8AK-AS

Page 1: ...ble Accessory Order Separately OMRON CT Commercially Available CTs If you use a commercially available CT do notexceed the overload capacity of the K8AK AS2 Refer to Safety Precautions for the K8AK Se...

Page 2: ...K8AK AS2 0 1 to 1 A AC DC Compatible with commercially available CTs 0 5 to 5 A AC DC Compatible with commercially available CTs 0 8 to 8 A AC DC K8AK AS3 When used with the OMRON CT K8AC CT200L 10 t...

Page 3: ...humidity rated power supply voltage DC or 50 60 Hz sine wave input Operating time 50 ms at 25 C and 65 humidity rated power supply voltage Applicable standards Conforming standards EN60947 5 1 Install...

Page 4: ...5 and 10 mm min Test method Relationship of Mounting Distance between K8AK AS Relays and Input Current Reference Values The following diagram shows the relationship between the mounting distances and...

Page 5: ...e notes 1 and 2 Terminal block See notes 1 and 2 Item Meaning Power indicator PWR Green Lit when power is being supplied Relay status indicator RY Yellow Lit when relay is operating Alarm indicator AL...

Page 6: ...input terminal Example K8AK AS3 Using Input Terminals I3 COM The maximum setting range will be 200 A AC and the setting range will be 20 to 200 A 2 Hysteresis Hysteresis is set using the hysteresis k...

Page 7: ...lashes when the set value and the input have reached the same level Use this as a guide to set the startup lock time The startup lock time will start when the input current reaches 30 or more of the s...

Page 8: ...ure for information on the motor startup current For a motor with a rating of 5 A the startup current will be approximately 30 A The startup current will exceed the overload capacity rating 150 for 1...

Page 9: ...s 2 Use and store the product in a location where the ambient temperature and humidity are within the specified ranges If applicable provide forced cooling 3 Mount the product in the correct direction...

Page 10: ...will be large if the K8AK AS K8AK AW K8AK VS or K8AK VW is used for thyristor or inverter control The K8AK PH K8AK PA K8AK PM K8AK PW or K8DS PH cannot be used on the secondary side of an inverter To...

Page 11: ...nt or addition to the above warranty See http www omron247 com or contact your Omron representative for pub lished information 14 Limitation on Liability Etc OMRON COMPANIES SHALL NOT BE LIABLE FOR SP...

Page 12: ...rasil 55 11 2101 6300 www omron com br OMRON ARGENTINA SALES OFFICE Cono Sur 54 11 4783 5300 OMRON CHILE SALES OFFICE Santiago 56 9 9917 3920 OTHER OMRON LATIN AMERICA SALES 54 11 4783 5300 OMRON INDU...

Reviews: