K8AK-AS
4
Connections
Wiring Diagram
●
Overcurrent Operation Diagram
(Output Relay Drive Method: Normally Open)
DIP switch setting: SW3 OFF.
●
Undercurrent Operation Diagram
(Output Relay Drive Method: Normally Closed)
DIP switch setting: SW3 ON.
Note: 1.
The K8AK-AS3 is designed to be used in combination with
the OMRON K8AC-CT200L Current Transformer (CT).
2.
There is no polarity when a DC current input is used.
3.
Refer to the
Setting Ranges and Wiring Connections
as the
explanation of current input l1, l2, and l3 terminal.
AS (I3 terminal)
0
10
10
60
50
40
30
20
5
15
Distance between products d [mm]
I = 3 A
I = 5 A
I = 1 A
I = 8 A
Ambient temperature [°C]
K8AK
No.3
K8AK
No.2
K8AK
No.1
K8AK
No.4
K8AK
No.5
DIN Track
Distance between products: d
Sample: K8AK-AS
Applied voltage: 240 VAC
Mounting distances: 0, 5, and 10 mm min.
Test method
●
Relationship of Mounting Distance between
K8AK-AS Relays and Input Current
(Reference Values)
The following diagram shows the relationship between the mounting
distances and the input current. If the relay is used with an input
current that exceeds these values, the temperature of the K8AK may
rise and shorten the life of the internal components.
Power supply
voltage
Set value
Input
Alarm indicator
Relay 11-14
Relay 11-12
Hysteresis
(
−
5% to 50% of operating value)
Lit
Flashing
T: Operating time (0.1 to 30 s)
Lock: Startup lock time (0 to 30 s)
LOCK
T
Power supply
voltage
Set value
Input
Relay 11-14
Relay 11-12
Alarm indicator
Lit
Flashing
Hysteresis
(5% to 50% of operating value)
T
T: Operating time (0.1 to 30 s)
Single-phase power
A1
Power supply
voltage
A2
Current
input
I1
I2
I3
COM
14
Signal
output
12
A1
A2
Current
input
I1
I2
I3
COM
14
Signal
output
12
Relay
signal
output
or
Load
Single-phase power
Relay
signal
output
Load
11
11
Power supply
voltage