44
Upper-limit Compensation Value
Lower-limit Compensation Value
The upper- and lower-limit values of the sensor can be shifted. If both the upper-
and lower-limit values are shifted by 2
°
C each, for example, a process value of
200
°
C will be treated as 202
°
C after compensation.
Temperature
Lower-limit value
Upper-limit value
Upper-limit
compensation value
After compensation
Before com-
pensation
Lower-limit
compensation value
Input (% FS)
Set value
Unit
Default
–1999 to 9,999
---
0
Follow the steps described below to set both the upper- and lower-limit compensation
values to 2.
Set Value LED Display Model
Basic Model
1, 2, 3...
1. Press the Mode Key for more than one second while the
opt
option menu is
displayed. The
aUg
average processing setting will appear.
Set Value LED Display Model
Basic Model
2. Press the Mode Key twice to display the
insh
upper-limit compensation val-
ue setting.
Set Value LED Display Model
Basic Model
insh
insl
FUNCTION
SETTING
SETTING
EXAMPLE
Setting Mode