109
Appendix C
List of Settings
Use this sheet to keep a record of set values.
Menu
Parameter
Setting range
Unit
Set value
sUset
sU.hh
HH set value
–1999 to 9,999
---
Setting value menu
sU. h
H set value
–1999 to 9,999
---
sU. l
L set value
–1999 to 9,999
---
sU.ll
LL set value
–1999 to 9,999
---
setup
Setup menu
inĆt
Input type
JPt100, Pt100, K1, K2, J1, J2, T,
E, L1, L2, U, N, R, S, B, W, PL
II
,
4 to 20 mA, 0 to 20 mA, 1 to 5 V,
0 to 5 V, 0 to 10 V
---
cĆĆf
°
C/
°
F display change
°
C/
°
F
---
inĆh
Scaling upper limit value
–1999 to 9,999
inĆl
Scaling lower limit value
–1999 to 9,999
decĆp
Decimal point position
%%%%
/
%.%%%
/
%%.%%
/
%%%.%
uĆno
Communications unit no.
0 to 99
---
bps
Baud rate
1,200/2,400/4,800/9,600/19,200/
38,400
bps
len
Word length
7/8
bit
sbit
Stop bits
1/2
bit
prty
Parity bits
None/Even/Odd
---
opt
Option menu
aUg
Average processing
No average processing
Movement average processing
times: 2, 4, 8, 16, or 32 times
Simple average processing times:
2, 4, 8, 16, or 32 times
---
digit
Display digit change
4/5 digits
---
insh
Upper-limit temperature
input compensation value
–1999 to 9,999
---
insl
Lower-limit temperature
input compensation value
–1999 to 9,999
---
his
Hysteresis
1 to 9,999
---
cĆout
Comparative output pattern
Standard, zone, or level output
---
stdby
Standby sequence
ON/OFF
---
lset.h
H linear output range
–1999 to 9,999
---
lset.l
L linear output range
–1999 to 9,999
---
rĆl
Remote/Local processing
Remote/Local
---