A3 Appendix GRT1-ECT Specifications
A3 - 2
GRT1-series EtherCAT Communication Unit - Operation Manual
A3-1 Specifications GRT1-ECT
This section explains the communication specifications of the GRT1-series EtherCAT Slave.
A3-1-1 Installation specifications
Item
Specification
Unit type
SmartSlice GRT1 series
Model
GRT1-ECT
Mounting position
DIN Rail mounted
Power supply
24 Vdc +10% -15% (20.4 to 26.4 Vdc)
Current consumption
130 mA typical at 24 VDC
Dimensions (W x H x D)
58 x 80 x 70mm
Weight
130g (typical)
A3-1-2 Environment specifications
Item
Specification
Ambient operating
temperature
–10 to 55°C (no icing or condensation)
Ambient operating
humidity
25% to 85% Relative Humidity
Storage temperature
10 to 57Hz, 0.7-mm amplitude
57 to 150Hz, acceleration: 49 m/s
2
Shock resistance
150 m/s
2
Dielectric strength
500 VAC (between isolated circuits)
Conformance to EMC and
Electrical safety standards
EN61131-2:2007
Enclosure rating
IP20
A3-1-3 SmartSlice I/O System specifications
Item
Specification
Number of connectable
SmartSlice I/O Units
64 Units max.
Connected directly to the GRT1-ECT or via turnback extension units.
Communication distance
SmartSlice I/O Units: 64 Units coupled (about 2 m max.)
Turnback Cable: 2 m max. (2 cables, 1 m each)
Turnback Cable
Length 1 m max., up to 2 cables can be connected.
SmartSlice I/O Unit
connections
Building-block style configuration with slide connectors (Units connect with
Turnback Cables).
Baseblock power supply
Voltage: 24 V DC
Current: 4 A max
Number of I/O data
512 digital inputs and 512 digital outputs max.
Total I/O data size 64 words (128 bytes)
Summary of Contents for GRT1-ECT SmartSlice
Page 3: ...GRT1 series EtherCAT Communication Unit Operation Manual Revised March 2012 ...
Page 18: ...15 GRT1 series EtherCAT Communication Unit Operation Manual ...
Page 30: ...1 EtherCAT Network 1 8 GRT1 series EtherCAT Communication Unit Operation Manual ...
Page 38: ...2 EtherCAT Communication details 2 8 GRT1 series EtherCAT Communication Unit Operation Manual ...
Page 52: ...4 GRT1 ECT Details 4 10 GRT1 series EtherCAT Communication Unit Operation Manual ...
Page 76: ...6 GRT1 ECT Troubleshooting 6 12 GRT1 series EtherCAT Communication Unit Operation Manual ...
Page 136: ...A4 Appendix Object Dictionary A4 16 GRT1 series EtherCAT Communication Unit Operation Manual ...
Page 140: ...Revision 2 GRT1 ECT series EtherCAT Slave Unit User s Manual ...