2. Characteristics
G9SX
USER'S GUIDE
79
Ratings and Spec
ifications
Se
ct
io
n
4
2-4 Expansion Unit
Note: 1.
When two or more Units are connected by logical AND, the operating time and response time are the sum total of the operating times and response
times, respectively, of all the Units connected by logical AND.
2.
This does not include the operating time or response time of Safety Guard Switching Units (G9SX-AD/-ADA/-NSA/-GS) that are connected.
3.
This does not include the operating time or response time of internal relays in the G9SX-EX-
@
.
4.
For the G9SX-
@
-RT (with screw terminals) only.
Item
Model
G9SX-EX-
@
Overvoltage category (IEC/EN 60664-1)
II (Safety relay outputs 13 to 43 and 14 to 44: III)
Operating time (OFF to ON state)
(See note 1.)
30 ms max. (See note 2.)
Response time (ON to OFF state)
(See note 1.)
10 ms max. (See note 2.)
ON-state residual voltage
3.0 V max. for safety outputs and auxiliary outputs
OFF-state leakage current
0.1 mA max. for safety outputs and auxiliary outputs
Maximum wiring length of safety input
and logical AND input
100 m max.
(External connection impedance: 100
Ω
max. and 10 nF max.)
Reset input time (Reset button pressing
time)
100 ms min.
Accuracy of OFF-delay time (See note 3.) Within
±
5% of the set value
Insulation
resistance
Between all terminals
connected together and DIN
rail
100 M
Ω
min. (at 500 VDC)
Dielectric
strength
Between all terminals
connected together and DIN
rail
1,200 VAC for 1 min
Between different poles of
outputs
Between safety relay outputs
connected together and
other terminals connected
together
2,200 VAC for 1 min
Vibration resistance
Frequency: 10 to 55 to 10 Hz, 0.375-mm single amplitude (0.75-mm double amplitude)
Shock
resistance
Destruction
300 m/s
2
Malfunction
100 m/s
2
Durability
Electrical
100,000 cycles min.
(rated load, switching frequency: 1,800 cycles/hour)
Mechanical
5,000,000 cycles min. (switching frequency: 7,200 cycles/hour)
Ambient operating temperature
−
10 to 55
°
C (with no icing or condensation)
Ambient operating humidity
25% to 85%
Terminal tightening torque (See note 4.)
0.5 N·m
Weight
Approx. 165 g
Summary of Contents for G9SX Series
Page 50: ...MEMO 50 G9SX USER S GUIDE ...
Page 95: ...G9SX USER S GUIDE 95 Precautions Precautions ...
Page 101: ...MEMO G9SX USER S GUIDE 101 ...
Page 102: ...MEMO 102 G9SX USER S GUIDE ...