1. Troubleshooting
G9SX
USER'S GUIDE
89
Ap
pe
nd
ix
ERR
indicator
Other
indicator
Fault
Expected causes of the fault
Check points and measures to take
Page
Lights
EI blinks
Fault involved with
instantaneous safety
outputs
(1) Instantaneous safety outputs short
circuited.
(1) Check the wiring to S14 and S24.
---
(2) Instantaneous safety outputs and 24 V,
0 V, or another I/O terminal short
circuited.
(2) Check the wiring to S14 and S24.
---
Fault involved with
logical AND
connection outputs
(3) Logical AND connection outputs and
24 V, 0 V, or another I/O terminal short
circuited.
(3) Check the wiring to L1.
---
Abnormal ambient
temperature
(4) The environment exceeds the
permissible ambient operating
temperature.
(4) Check the ambient temperature and
spacing around the G9SX.
78
Failure in internal
circuit
(5) Failure in internal circuit for S14 and
S24.
(5) Replace the G9SX.
---
(6) Failure in internal circuit for L1.
(6) Replace the G9SX.
---
ED blinks
Fault involved with
OFF-delayed safety
outputs
(1) Safety OFF-delayed outputs short
circuited.
(1) Check the wiring to S44 and S54.
---
(2) Wiring to the OFF-delayed safety
contact outputs and 24 V, 0 V, or
another I/O terminal short circuited.
(2) Check the wiring to S44 and S54.
---
Incorrect set values
for OFF-delay time
(3) Settings of two OFF-delay time preset
switches are not the same.
(3) Confirm the set values of the OFF-
delay time preset switches on the front
and back of the Unit.
65
Abnormal ambient
temperature
(4) The environment exceeds the
permissible ambient operating
temperature.
(4) Check the ambient temperature and
spacing around the G9SX.
78
Failure in internal
circuit
(5) Failure in internal circuit for S44 and
S54.
(5) Replace the G9SX.
---
(6) OFF-delay time preset switch failed.
(6) Replace the G9SX.
---
AND blinks
Fault involved with
logical AND
connection input
(1) Logical AND connection input and 24 V,
0 V, or another I/O terminal short
circuited.
(1) Check the wiring to T41.
---
(2) Maximum cable length exceeded.
(2) Make sure that the wiring length for the
T41 and T42 terminals is less than 100 m.
---
(3) Maximum number of connected Units
exceeded.
(3) Check the logical AND connection for
the G9SX.
59
Incorrect setting for
logical AND
connection setting
switch
(4) The logical AND connection preset
switch is set to OFF.
(4) When using a logical AND connection,
set the logical AND connection preset
switch to AND.
57
Fault in internal
circuit
(5) Failure in internal circuit for T41 and
T42.
(5) Replace the G9SX.
---
(6) The logical AND connection preset
switch failed.
(6) Replace the G9SX.
---
UA blinks
Fault in external
indicator output
(1) Wiring to the external indicator output
and 24 V, 0 V, or another I/O terminal
short circuited.
(1) Check the wiring to UA.
---
(2) External indicator output disconnected.
(external indicator not connected)
(2) Check the wiring to UA.
68
Failure of the
external indicator
(3) External indicator failed.
(3) Replace the connected external
indicator.
---
Fault in the external
indicator diagnosis
switching input
(4) Wiring for external indicator diagnosis
switching input and 24 V disconnected.
(when external indicator was not
connected)
(4) Check the wiring to Y3.
68
Failure in internal
circuit
(5) Failure in internal circuit for UA.
(5) Replace the G9SX.
---
(6) Failure in internal circuit for Y3.
(6) Replace the G9SX.
---