G-130

Safety Sensors / Components

Precautions

Wiring

Turn OFF the G9SB before wiring. Do not touch the terminals 

of the G9SB while the power is turned ON, because the termi-

nals are charged and may cause an electric shock.

Use the following to wire the G9SB.

Stranded wire:0.2 to 2.5 mm

2

Solid wire:0.2 to 2.5 mm

2

Tighten each screw to a torque of 0.5 to 0.6 N·m, or the G9SB 

may malfunction or generate heat. 

External inputs connected to T11 and T12 or T21 and T22 of 

the G9SB must be no-voltage contact inputs.

Applicable Safety Category

G9SB-200

#

-

#

/301

#

-

#

 meet the requirements of Safety Cate-

gory 4 of the EN954-1 standards when they are used as 

shown in the examples provided by OMRON. Relays may not 

meet the standards in some operating conditions. The G9SB-

3010 can be applied to Safety Category 3 of the EN954-1 us-

ing double breaking. The applicable safety category is deter-

mined from the whole safety control system. Make sure that 

the whole safety control system meets EN954-1 requirements.

Mounting Multiple Units

When mounting multiple Units close to each other, the rated 

current will be 3 A. Do not apply a current higher than 3 A.

Connecting Inputs

If using multiple G9SB models, inputs cannot be made using 

the same switch. This is also true for other input terminals.

Earth Short

A positive thermistor is built into the G9SB circuits, so you can 

detect earth short breakdowns and breakdown shorts be-

tween channel 1 and channel 2. (Detection of breakdown 

shorts between channel 1 and channel 2 is supported for 

G9SB-2002-

#

/3012-

#

 models only.)

Note: In order to detect earth short breakdowns, connect the minus side of the

power supply to ground.

T11 T12

T11 T12

G9SB

G9SB

In the interest of product improvement, specifications are subject to change without notice.

ALL DIMENSIONS SHOWN ARE IN MILLIMETERS.

To convert millimeters into inches, multiply by 0.03937. To convert grams into ounces, multiply by 0.03527.

Cat. No. 

J130-E2-01-X

F502-EN2-04.book  Seite 130  Dienstag, 26. Juli 2005  5:48 17

Summary of Contents for G9SB

Page 1: ...hannel or 2 channel input possible 0 None direct breaking 2 2 channel input 6 Miscellaneous A Auto reset inverse input B Auto reset common input C Manual reset inverse input D Manual reset common inpu...

Page 2: ...9SB 3010 G9SB 301 Resistive load cos 1 Rated load 250 VAC 5 A Rated carry current 5 A Item G9SB 200 G9SB 3010 G9SB 301 Contact resistance See note 1 100 m Operating time See note 2 30 ms max Response...

Page 3: ...T22 Feedback loop Control circuit Timing Chart Limit switches S1 and S2 K1 and K2 NC K1 and K2 NO KM1 and KM2 NC KM1 and KM2 NO S1 Safety limit switch with direct opening mechanism D4N or D4B S2 Limit...

Page 4: ...rrupted Reset switch S1 K1 and K2 NC K1 and K2 NO KM1 and KM2 NC KM1 and KM2 NO Note Output turns ON with the rising edge of re set switch S1 but will not operate if there is a short breakdown in S1 F...

Page 5: ...1 12 23 24 S2 S1 KM1 KM2 K1 K2 K1 K1 K2 K2 K1 a a K2 TH SA A1 A2 T31 T32 13 23 33 41 14 24 34 42 Open Feedback loop Control circuit Timing Chart Limit switches S1 and S2 K1 and K2 NC K1 and K2 NO KM1...

Page 6: ...24 34 PWR K1 K2 PWR K1 K2 83 18 2 5 68 48 2 6 2 5 10 112 max 100 max 18 max Average 17 5 Terminal Arrangement G9SB 200 G9SB 3010 green green orange orange orange orange 83 18 2 5 68 48 2 6 13 23 33 T1...

Page 7: ...2 It is not possible to wire G9SB 2 A C models for 1 channel input 2 Only G9SB 301 models have terminals 33 34 and 41 42 K1 K2 K1 K1 K2 K2 K1 a a K2 TH SA A1 A2 T11 T12 T31 T32 13 23 33 41 14 24 34 42...

Page 8: ...ry is deter mined from the whole safety control system Make sure that the whole safety control system meets EN954 1 requirements Mounting Multiple Units When mounting multiple Units close to each othe...

Reviews: