background image

12

F3SG-SR-K

Quick Installation Manual

7. Pre-Operation Checklists / Maintenance Checklists

After wiring, mounting and beam alignment are done, check the operation of the F3SG-SR-K.

Pre-Operation Checklists

After installation, the highest level administrator must use the following checklist to verify the operation, plac

-

ing a check mark in each of the boxes.

Checklists

- Installation Condition Check

The machine itself does not prevent the operation of safety functions such as stopping.

The hazardous part of a machine cannot be reached without passing through the detection zone of the

F3SG-SR-K.

The  system is configured so that  the  F3SG-SR-K  can always detect a worker who is  working  in the

hazardous zone.

The interlock reset switch is installed in a location that provides a clear view of the entire hazardous zone

and it cannot be activated from within the hazardous zone.

The pre-reset switch is installed in a location inside the hazardous zone and where it cannot be operated

from outside the hazardous zone.

Safety distance has been calculated. Calculated distance: S = ( )mm

Safety distance has been calculated with larger object resolution when the Floating Blanking or Reduced

Resolution function is used. Calculated distance: S = ( )mm

The actual distance is equal to or greater than the calculated distance. Actual distance = ( )mm

Reflective surfaces are not installed in prohibited zones.

Not installed in a retro-reflective configuration.

When the Muting function is used, a muting sensor must be installed so that MUTING state should not

occur when a human body enters a detection zone of the F3SG-SR-K by mistake.

When the Muting function is used, a muting sensor must be installed so that MUTING state should not

occur when a human body enters a hazardous zone of a machine.

When the Muting function is used, MUTING state can be checked from where a worker operates or adjust

the machine.

A muting sensor consists of two independent devices.

It is not used in flammable or explosive atmosphere.

- Wiring Check Before Power Is Turned ON

When the power supply unit is connected to multiple devices, the power supply unit must have tolerance

against total rated current of the devices.

The power supply unit is a 24 VDC unit that conforms to the EMC Directive, Low-voltage Directive, and

output holding time specifications.

The power supply lines are wired with a proper polarity according to the wiring specifications of the PNP

or NPN setting.

Emitter/receiver cables are properly connected to the respective emitters/receivers.

Double insulation is used between I/O lines and the hazard potential (commercial power supplies, etc.).

When using PNP output, the outputs are not short-circuited to +24 VDC line. When using NPN output,

the outputs are not short-circuited to 0 VDC line.

When using PNP output, loads are not connected to +24 VDC line. When using NPN output, loads are

not connected to 0 VDC line.

All lines are not connected to commercial power source.

Model of emitter and receiver must be the same.

When two or more F3SG-SR-K systems are used, they are prevented from mutual interference with each

other.

Neither bracket must be loose.

Auxiliary output must not be used as safety output.

When using PNP output, +24 VDC line of the power supply must not be grounded. When using NPN

Mounting

Wiring

Operation check

Summary of Contents for F3SG-SR-K Series

Page 1: ...re Circuit Diagram 3 5 Wiring Examples 4 5 1 Non Muting System Wiring Example Auto Reset Mode with EDM Unused 4 5 2 Muting System Wiring Examples Standard Muting Mode Exit Only Muting mode 4 6 Mountin...

Page 2: ...bled Auxiliary Output Safety output information Inverted signal output Enable Muting Standard Muting Mode Override Enabled Emitter Receiver 7 6 1 4 3 2 10 9 1 4 3 2 7 6 5 Emitter Emitter Receiver Loca...

Page 3: ...24V 0V Brown Black TEST White COM Blue Brown Yellow White OSSD 2 Pink MUTE B COM Gray MUTE A PRE RESET PSDI COM Black OSSD 1 Red AUX Blue Muting input circuit A Reset input circuit Muting input circu...

Page 4: ...iver Emitter S1 Test switch Connect the line to 0V 24V blue of the emitter if this switch is not required S2 Lockout reset switch override switch or override cancel switch S3 S4 Muting sensor PLC Prog...

Page 5: ...mitter and receiver units must be set to the same scan code for the receiver to enter the MACHINE RUN state The scan code is selectable by the End Caps on the emitter and receiver units The F3SG SR K...

Page 6: ...S Safety distance mm Tm Machine s response time s Ts Response time of the F3SG SR from ON to OFF s d Detection capability or object resolution of the F3SG SR mm Calculation Example for Systems with L...

Page 7: ...digit number of the type name Protective height Dimension D F3SG SR 14 C 20 F3SG SR 25 Dimension H C 170 Dimension I C 200 Unit mm Use the brackets of specified quantities and locations according to...

Page 8: ...brackets to the wall are not included 2 Loosen the alignment screws of the bracket hexagon socket head cap screw M5 15 to remove the bracket 1 Fig 2 M8 M8 Fig 1 Align in the same line Bracket 1 Bracke...

Page 9: ...no longer drops Fig 3 4 Power the emitter and receiver on to perform beam alignment There is no restriction in the angle adjustment range Groove of the sensor s cap Bracket 2 Bracket 2 Groove of the s...

Page 10: ...ing The recommended torque to tighten these screws is 3 0 N m Fig 5 Tightening screws with a torque that considerably exceeds the recommended torque may cause failure Alignment screws Fig 5 Securely t...

Page 11: ...the emitter and receiver not in parallel to each other or misaligned may fail to operate properly Proper orientation Wrong orientation BTM mark Align the positions of the BTM marks Detection field Al...

Page 12: ...uman body enters a detection zone of the F3SG SR K by mistake When the Muting function is used a muting sensor must be installed so that MUTING state should not occur when a human body enters a hazard...

Page 13: ...cator turns red when the TEST line is short circuited to 9 V to Vs When NPN is selected the OSSD indicator turns red when the TEST line is short circuited to 0 to 3 V When the External Device Monitori...

Page 14: ...ocked state the OSSD indicator remains red The reset input turns the OSSD indicator to green When the power of the F3SG SR K is turned ON while nothing is in the detection zone it must operate as foll...

Page 15: ...Floating Blanking or Reduced Resolution function is changed Calculated distance S mm When the Muting function setting is changed a muting sensor must be installed so that the MUTING state should not...

Page 16: ...31 2356 81 300 Fax 31 2356 81 388 OMRON ELECTRONICS LLC 2895 Greenspoint Parkway Suite 200 Hoffman Estates IL 60169 U S A Tel 1 847 843 7900 Fax 1 847 843 7787 OMRON ASIA PACIFIC PTE LTD No 438A Alexa...

Page 17: ...F3SG SR K IP69K F3SG SR K F3SG SR K http www fa omron co jp 1 2 2 2 3 3 4 3 5 4 5 1 EDM 4 5 2 4 6 5 6 1 IP69K F39 LSGTB K 5 7 9 9 F3SG SR F3SG PG SGFM 726 F3SG SR K OMRON Corporation 2020 All Rights...

Page 18: ...SG SR PG 2 F3SG SR K 1 1 F3SG SR PG 2 7 1 EDM 7 6 1 4 3 2 10 9 1 4 3 2 7 6 5 F3SG SRB CODE C ERR E LONG L TEST T CODE C ERR E OSSD O MAINT M PNP P CFG F SEQ S TOP BTM TOP BTM ON OFF PNP NPN 1 2 3 4 6...

Page 19: ...3 F3SG SR K 3 DIP SW SD Manager 3 F3SG SR PG 4 F3SG SR K 3 5 9 24V 0V 2 MUTE B MUTE A PSDI 1 A B 0V 24V ABI 2 ABI 1 PNP NPN PNP NPN...

Page 20: ...r 3 F3SG SR K F3SG SR K EDM EDM 1 NPN PNP NPN 2 0V DC24V NPN 1 DC24V S3 S4 4 IN PLC 5 6 7 S1 S2 1 2 24V 0V 2 24V 0V 0V 24V 0V 24V MUTE B MUTE A 3 8 S1 0V 24V S2 S3 S4 PLC IN1 IN2 DIP SW SD Manager 3 E...

Page 21: ...5 F3SG SR K 6 6 1 IP69K F39 LSGTB K 6 H 15 C 97 10 H 103 2 M8 60 82 20 I D 40 70 10 8 5 IP69K F39 LSGTB K IP69K F39 LSGTB K C 4 D F3SG SR 14 C 20 F3SG SR 25 H C 170 I C 200 mm...

Page 22: ...6 F3SG SR K 1 F39 LSGTB K 1 2 M5 15 1 2 M8 M8 1 M5 15 M5 15 1 1 2...

Page 23: ...7 F3SG SR K 3 2 1 3 4 2 2 3 4...

Page 24: ...8 F3SG SR K 5 3 0N 5 5...

Page 25: ...R K E ERR O OSSD M MAINT P PNP F CFG TOP BTM L LONG E ERR O OSSD E ERR S SEQ M MAINT F3SG SR PG http www fa omron co jp Web 0120 919 066 8 00 21 00 365 FAX Web PHS IP 055 982 5015 FAX 055 982 5051 www...

Reviews: