![Omron E5CS-U User Manual Download Page 97](http://html.mh-extra.com/html/omron/e5cs-u/e5cs-u_user-manual_744347097.webp)
Burnout/Short-circuit Display and Causes
A-7
Appendices
Burnout/Short-circuit Display and Causes
The display window shows the error details if an input sensor burnout or short-circuit occurs.
The error display and control output operation for burnouts and short-circuits is explained below
for each input type.
●
Thermocouple
Status
Display
Control output
Burnout
fff
flashing
OFF
•
The room temperature is displayed if an input short-circuit occurs.
●
Platinum Resistance Thermometer
Status
Display
Control output
Models with
Terminal
Blocks
Plug-in Models
fff
flashing
OFF
---
flashing
OFF
Burnout
2 or 3 wires disconnected
fff
flashing
OFF
Short-
circuit
---
flashing
OFF
•
The resistance value for platinum resistance thermometers is 100
Ω
at 0°C and 140
Ω
at
100°C.
●
Thermistor
Status
Display
Control output
Burnout
---
*
ON during heating
control (reverse
operation)
OFF during cooling
control (direct operation
)
Short-
circuit
fff
*
OFF during heating
control (reverse
operation)
ON during cooling control
(direct operation)
*
The display does not flash.
③
④
⑤
③
④
⑤
③
②
①
③
②
①
③
②
①
③
④
⑤