Section 5 Parameters
5-12
P
a
ra
meters
ALM mode
Integral time setting unit
Hysteresis width
Temperature width in which the
■
deviation
indicator lights
•
Select the integral time setting unit.
•
Set the hysteresis width.
•
Set the temperature width in which the
■
deviation indicator lights.
•
Set the integral time setting unit either to seconds or minutes in the initial
setting level (2).
•
The hysteresis width enables stable operation at the ON/OFF switching point
for ON/OFF control. The default setting is 0.1% FS for multi-input
(thermocouple/platinum resistance thermometer) models, and 0.2% FS for
other input types.
•
The default setting for the temperature width in which the
■
deviation
indicator lights is ±0.25% FS for multi-input (thermocouple/platinum
resistance thermometer) models, and ±1% FS for other input types.
100’s digit
10’s digit
1’s digit
Displayed
number
Integral time
setting unit
Hysteresis width
(ON/OFF control)
Temperature width
in which
■
deviation indicator
lights
O
Second
0% FS
0% FS
1
Minute
0.05% FS
±0.1% FS
2
0.1% FS
±0.25% FS
3
0.2% FS
±0.5% FS
4
0.3% FS
±0.75% FS
5
0.5% FS
±1% FS
6
0.75% FS
±1.25% FS
7
1% FS
±1.5% FS
8
1.5% FS
±1.75% FS
9
2% FS
±2% FS
Function
Setting