Parameters Related to Alarm Delays
Parameter name
Setting
Set (monitor)
values
Alarm 1 ON Delay
Initial setting level (4)
SP mode
0 to 999 (s)
Alarm 2 ON Delay
Initial setting level (5)
SP mode
0 to 999 (s)
Alarm 1 OFF Delay
Initial setting level (4)
ALM mode
0 to 999 (s)
Alarm 2 OFF Delay
Initial setting level (5)
ALM mode
0 to 999 (s)
* The defaults are 0, i.e., the ON and OFF delays are disabled.
Operating Procedure
Use the following procedure to set ON and OFF delays for the alarm
1 function.
An ON delay of 5 s and an OFF delay of 10 s will be set.
1.
Select the initial setting level (4).
2.
Select the “alarm 1 ON delay” (SP mode) parameter by pressing
the
M
key.
3.
Press the
U
and
D
Keys to set the parameter to 5.
4.
Press the
M
key to select the “alarm 1 OFF delay” (ALM mode)
parameter.
5.
Press the
U
and
D
Keys to set the parameter to 10.
M
M
Initial setting level (4)
SP mode
・
Alarm 1 ON delay
ALM mode
・
Alarm 1 OFF delay
0
SP ALM
ALM
1
2
OUT
0
1
2
ALM
ALM
SP
OUT
-
4
-
1
2
ALM
ALM
SP
OUT
5
SP ALM
ALM
1
2
OUT
0
1
2
ALM
ALM
SP
OUT
1
U
/
D
U
/
D
4.5 Alarm Delays
Summary of Contents for E5CS-U
Page 2: ......
Page 17: ...xv ...
Page 63: ...Section 4 Operations for Applications 4 10 Operations for Applications ...