3.1 Setting the Input Type
3-3
Basic
Oper
ations
●
Thermistor
●
Multi-input (Thermocouple/Platinum Resistance Thermometer) Models
Control Mode Switch 5:
OFF
Control Mode Switch 5:
ON
Specifications
Temper-
ature
range
Input temperature range
6 K
Ω
(0
°
C)
0 -50
to
50
(
°
C)
/
-50 to
100
(
°
F)
6 K
Ω
(0
°
C)
1
0 to
100
(
°
C)
/ 0 to
200
(
°
F)
30 K
Ω
(0
°
C)
2 50
to
150
(
°
C)
/ 100 to
300
(
°
F)
550
Ω
(200
°
C)
3 100
to
200
(
°
C)
/ 200 to
400
(
°
F)
4 K
Ω
(200
°
C)
4 150
to
300
(
°
C)
/ 300 to
600
(
°
F)
6 K
Ω
(0
°
C)
5 -50
to
50
(
°
C)
/
-50 to
100
(
°
F)
6 K
Ω
(0
°
C)
6 0
to
100
(
°
C)
/ 0 to
200
(
°
F)
30 K
Ω
(0
°
C)
7 50
to
150
(
°
C)
/ 100 to
300
(
°
F)
550
Ω
(200
°
C)
8 100
to
200
(
°
C)
/ 200 to
400
(
°
F)
THE
4 K
Ω
(200
°
C)
9 150
to
300
(
°
C)
/ 300 to
600
(
°
F)
•
The default is 1. If the setting is changed to a temperature range that goes
below 0
°
C, the minimum value inside the SP range will be automatically used
as the SP. The SP will be displayed when the power is turned ON.
•
The control range depends on the setting numbers, as follows:
Input setting numbers 0 and 5:
−
50 to +60
°
C
Input setting numbers 2 and 7:
0 to 160
°
C or 35 to 320
°
F
Input setting numbers 3 and 8:
0 to 210
°
C or 35 to 420
°
F
Input setting numbers 4 and 9:
25 to 315
°
C or 80 to 630
°
F
Others:
−
10% to 10% FS
Specifications
Temper-
ature
range
Input temperature range
0
-99 to 1300 (
°
C)
/
-99 to
1999
(
°
F)
K
1 0.0
to
199.9
(
°
C)
/
0.0 to
199.9
(
°
F)
2 -99
to
850
(
°
C)
/ -99 to
1500
(
°
F)
J
3 0.0
to
199.9
(
°
C)
/ 0.0 to
199.9
(
°
F)
L 4
-99
to
850
(
°
C)
/ -99 to
1500
(
°
F)
5 -99
to
400
(
°
C)
/
-99 to
700
(
°
F)
T
6 0.0
to
199.9
(
°
C)
/
0.0 to
199.9
(
°
F)
U 7
-99
to
400
(
°
C)
/ -99 to
700
(
°
F)
N 8
-99
to
1300
(
°
C)
/ -99 to
1999
(
°
F)
R 9
0
to
1700
(
°
C)
/
0 to
1999
(
°
F)
Specifications
Temper-
ature
range
Input temperature range
0
-99 to 850 (
°
C)
/
-99 to
1500
(
°
F)
1 0.0
to
199.9
(
°
C)
/ 0.0 to
199.9
(
°
F)
2 -99
to
99
(
°
C)
/ -99 to
99
(
°
F)
3 0
to
200
(
°
C)
/ 0 to
200
(
°
F)
Pt100
4 0
to
400
(
°
C)
/ 0 to
400
(
°
F)
5 -99
to
500
(
°
C)
/ -99 to
900
(
°
F)
6 0.0
to
199.9
(
°
C)
/ 0.0 to
199.9
(
°
F)
7 -99
to
99
(
°
C)
/ -99 to
99
(
°
F)
8 0
to
200
(
°
C)
/ 0 to
200
(
°
F)
JPt100
9 0
to
400
(
°
C)
/
0 to
400
(
°
F)
•
The default is 0.
•
The control range is ±20
°
C
or ±40
°
F of the input temperature range.
•
If unit is changed to 1 degree when the SP and alarm value for the
temperature range are displayed in 0.1-units from 0.0 to 199.9, 0.0 to
99.9 or 0.0 to 50.0, the values will be multiplied by 10 (e.g., 0.5
becomes 5). If the unit is changed in the reverse direction, the values
will be divided by 10. After changing the range, reset the Controller.