5.7 Initial Setting Level (4)
5-21
P
a
ra
meters
SP mode
Alarm 1 ON delay
Alarm 1 function is prevented from turning ON until after the delay time set in this parameter has
elapsed.
•
Set the time for which the ON delay is to be enabled.
•
To disable the ON delay, set 0.
Parameter Setting
range
Unit
Default
Alarm 1 ON delay
0 to 999
Second
0
* This parameter is displayed regardless of the output assignment
setting.
ALM mode
Alarm 1 OFF delay
Alarm 1 function is prevented from turning OFF until after the delay time set in this parameter has
elapsed.
•
Set the time for which the OFF delay is to be enabled.
•
To disable the OFF delay, set 0.
Parameter Setting
range
Unit
Default
Alarm 1 OFF delay
0 to 999
Second
0
* This parameter is displayed regardless of the output assignment
setting.
Function
Setting
Function
Setting