Section 5 Parameters
5-26
P
a
ra
meters
IS mode (1) Alarm 2 type
al
•
Select one of the following nine alarm 2 types:
Set
value
Alarm type
Alarm output
operation
0
Alarm function OFF
Output OFF
1
Upper- and lower-limit
2
Upper-limit
3 Lower-limit
4
Upper- and lower-limit range
5
Upper- and lower-limit with
standby sequence
6
Upper-limit with standby
sequence
7
Lower-limit with standby
sequence
8 Absolute-value
upper-limit
* Alarm values 1 to 7: Set the deviation from the SP (set point) in the
alarm value (X).
Alarm 8: Set the absolute value from 0°C/°F in the alarm value (Y).
* The default is 2 (upper-limit alarm).
*
This parameter is displayed regardless of the output assignment
setting.
OFF
ON
SP
X
X
ON
OFF
SP
X
X
OFF
ON
SP
X
X
OFF
ON
SP
X
OFF
ON
SP
X
OFF
ON
SP
X
OFF
ON
SP
X
OFF
ON
0
Y
Function
Setting