Section 1 Overview
1-12
Ov
er
vie
w
●
Alarm Mode
Switch
•
Select the alarm mode switch number when changing to the alarm
mode. This switch is not provided in models without alarms.)
Set
value
Alarm type
Alarm output
operation
0,9
Alarm function OFF
Output OFF
1
Upper- and lower-limit
2
Upper-limit
3 Lower-limit
4
Upper- and lower-limit range
5
Upper- and lower-limit with
standby sequence
6
Upper-limit with standby
sequence
7
Lower-limit with standby
sequence
8 Absolute-value
upper-limit
* Alarm values 1 to 7: Set the deviation from the SP (set point) in
the alarm value (X).
Alarm 8: Set the absolute value from 0°C/°F in the alarm value (Y).
* The default is 2 (upper-limit alarm).
OFF
ON
SP
X
X
OFF
ON
SP
X
X
ON
OFF
SP
X
X
OFF
ON
SP
X
OFF
ON
SP
X
OFF
ON
SP
X
OFF
ON
SP
X
OFF
ON
0
Y