background image

E5CK-T

  E5CK-T

171

Specifications

J

RATINGS

Model

E5CK-T (Standard)

E5CK-T (24 V Type)

Supply voltage

100 to 240 VAC, 50/60 Hz

24 VAC/VDC, 50/60 Hz

Power consumption

15 VA

6 VA, 3.5 W

Operating voltage range

85% to 110% of rated supply voltage

Input

Thermocouple

K, J, T, E, L, U, N, R, S, B, W, PLII

Platinum resistance
thermometer

JPt100, Pt100

Current input

4 to 20 mA, 0 to 20 mA

Voltage input

1 to 5 V, 0 to 5 V, 1 to 10 V

Input impedance

Current input

150 

Voltage input

1 M

 min.

Control output

According to Output Board (see Output Board Ratings and Characteristics)

Auxiliary output

SPST-NO, 1 A at 250 VAC (resistive load)

Control method

ON/OFF or advanced PID control

Setting method

Digital setting using front panel keys or communications features

Indication method

7-segment digital display and LEDs

Additional functions

Standard

Manual output, heating/cooling control, SP limiter, loop burnout alarm, MV limiter,
MV change rate limiter, input digital filter, input shift, run/reset, protect functions,
scaling function

J

CHARACTERISTICS

Indication accuracy 

Thermocouple

±

0.3% of indication value or 

±

1

°

C, whichever greater, 

±

1 digit max.

(See Note 1)

Platinum resistance 
thermometer

±

0.2% of indication value or 

±

0.8

°

C, whichever greater, 

±

1 digit max.

Analog input

±

0.2% of indication value, 

±

1 digit max.

Hysteresis

0.01% to 99.99% FS (in units of 0.01% FS)

Proportional band (P)

0.1% to 999.9% FS (in units of 0.1% FS)

Integral (reset) time (I)

0 to 3,999 s (in units of 1 s)

Derivative (rate) time (D)

0 to 3,999 s (in units of 1 s)

Control period

1 to 99 s (in units of 1 s)

Manual reset value

0.0% to 100.0% (in units of 0.1%)

Alarm setting range

–1,999 to 9,999 or –199.9 or 999.9 (decimal point position dependent on input type)

Set time

0 to 99 hrs 59 min or 0 to 99 min 59 s

Program capacity

1 pattern, 16 steps (possible to use up to 4 patterns with the communications func-
tion.)

Programming method

Time or ramp setting method

Time accuracy

±

0.2% (

±

500 ms) of the set value

Sampling period 

Temperature input

250 ms

(See Note 2)

Analog input

100 ms

Insulation resistance

20 M

 min. (at 500 VDC)

Dielectric strength

2,000 VAC, 50/60 Hz for 1 min between terminals of different polarities

(This table continues on the next page.)

Note: 1. The indication accuracy of the K1, T, and N thermocouples at a temperature of -100

°

C max. is 

±

2

°

±

1 digit maximum. The

indication accuracy of the U and L thermocouples at any temperature is 

±

2

°

±

1 digit maximum.

The indication accuracy of the B thermocouple at a temperature of 400

°

C max. is unrestricted.

The indication accuracy of the R and S thermocouples at a temperature of 200

°

C max. is 

±

3

°

±

1 digit maximum.

The indication accuracy of the W thermocouple at any temperature is (

±

0.3% of the indicated value or 

±

3

°

C, whichever is great-

er) 

±

1 digit maximum. The indication accuracy of the PLII thermocouple at any temperature is (

±

0.3% or 

±

2

°

C, whichever is

greater) 

±

1 digit maximum.

2. The sampling period of the standard model with CT and remote SP inputs is 250 ms.

Summary of Contents for E5CK-AA1-500 AC100-240

Page 1: ...H High accuracy 100 ms sampling for analog input H Conforms to international EMC and safety standards H 24V AC DC type also available H 3 year warranty RC Ordering Information Order control output boa...

Page 2: ...DE0106 part 100 E5CK T 1 E53 COV07 Software For setup and monitoring requires optional computer communications board All 1 SYS CONFIG V2 0 Temperature Ranges Platinum Resistance Thermometer Input swit...

Page 3: ...units of 0 1 FS Integral reset time I 0 to 3 999 s in units of 1 s Derivative rate time D 0 to 3 999 s in units of 1 s Control period 1 to 99 s in units of 1 s Manual reset value 0 0 to 100 0 in unit...

Page 4: ...contact discharge level 2 8kV air discharge level 3 Immunity RF interference ENV50140 10V m amplitude modulated 80 MHz to 1 GHz level 3 10 V m pulse modulated 900 MHz Immunity Conducted Disturbance E...

Page 5: ...rd model set up the output boards for control outputs 1 and 2 before mounting the Controller 2 On a position proportional model the relay output board is already set so this setup operation is unneces...

Page 6: ...74 Dimensions Unit mm inch J E5CK T 60 2 36 min Panel Cutouts 65 2 56 min 48 1 89 58 2 28 13 3 0 52 100 3 94 53L x 53W 44 8 X 44 8 J ACCESSORIES ORDER SEPARATELY Terminal Cover E53 COV07 44 3 1 74 44...

Page 7: ...arefully pull the internal mechanism from the housing Refer to the drawing below J SETTING UP THE OUTPUT BOARD 1 Two rectangular holes are provided on the power board right side of Controller Fit the...

Page 8: ...cm Adapter Panel Watertight packing Input Jumper Setting Note The jumper is factory set to TC S PT temperature input Set the jumper to temperature voltage or current input according to the sensor con...

Page 9: ...s from external noise Solderless terminals are recommended when wiring the Controller Tighten the terminal screws using a torque no greater than 0 78 N S m or 8 kgf S cm max Be careful not to tighten...

Page 10: ...eter inputs set the inputs to a common position TC PT as the temperature input Control Output Terminal numbers 11 and 12 are for control output 1 OUT1 The five output types and internal equalizing cir...

Page 11: ...8 7 6 13 14 11 12 3 2 Relay specifications are as follows SPST NO 250 VAC 1 A Option Terminal numbers 1 13 and 14 are valid only when the option board is set in the Controller The following four conn...

Page 12: ...ay key sp0 0 4 Set the target value to 50 Target value Display key 50 sp0 Step number display 5 Press the Display Key to shift to the display for the time of Step 0 Time parameter for step 0 Step time...

Page 13: ...C 199 9 to 999 9 F Platinum resistance 1 Pt100 199 9 to 650 0 C 199 9 to 999 9 F thermometer 2 K1 200 to 1 300 C 300 to 2 300 F Thermocouple 3 K2 0 0 to 500 0 C 0 0 to 900 0 F 4 J1 100 to 850 C 100 t...

Page 14: ...and 2 and auxiliary outputs 1 and 2 The assignment destination of each output function is restricted Refer to the tables provided under the headings Standard Models and Position Proportionate Models...

Page 15: ...ce deviation X SP ON OFF X SP ON OFF 7 Lower limit alarm with standby sequence deviation X SP ON OFF X SP ON OFF 8 Absolute value upper limit alarm X 0 ON OFF 0 X ON OFF 9 Absolute value lower limit a...

Page 16: ...e alarm 1 to 3 open in alarm parameters setup mode Factory setting is close in alarm n o J PARAMETER OPERATION LIST Switching to modes other than manual or protect mode is carried out using the mode s...

Page 17: ...AT auto tuning set up the control period change PID parameters and set alarm values Level 2 Mode This is the auxiliary mode for adjusting control In this mode you can set the parameters for limiting...

Page 18: ...tors remote SP in the local SP mode Set Point During SP Ramp Monitors the set point when the SP ramp function is used J PROTECT MODE Press twice for 1 s min Security Key protect To level 0 Press twice...

Page 19: ...arameter of the Controller in standard control is 0 Hysteresis Heat Available when the Controller is in ON OFF control For heating cooling control Hysteresis Cool Available when the Controller is in O...

Page 20: ...ut Shift Lower Limit Available if the input type is a thermocouple or platinum resistance thermometer See Input Shift For models E5AK EK T only Open Close hysteresis Standby time Input Shift Temperatu...

Page 21: ...are used J OPTION MODE Event Input Assignment 1 Available for the event input function Event Input Assignment 2 Available for the event input function For models E5AK E5EK T only Event Input Assignme...

Page 22: ...t value step 0 time step 1 target value and step 1 time The step target value can be set within a range between the lower and upper target value limits The default value is zero The step time can be s...

Page 23: ...p 0 Set the ON OFF timing with the timing signal 1 2 ON time and time signal 1 2 OFF time parameters in Program mode ON Conditions If the ON time is shorter than the OFF time the signal will be reset...

Page 24: ...mal the probable cause may be external noise affecting the control system Check for external noise Operation at Error Control output functions turn OFF 2 mA max at 4 to 20 mA output and output equival...

Page 25: ...ol continues allowing normal operation Motor Calibration Error Displayed on the No 2 Display Meaning Motor calibration has ended with an error Action First correctly connect the wiring for the potenti...

Page 26: ...Unit must be approximately 0 78 N S m or 8 kgf S cm Use the following type of solderless terminals for M3 5 screws 7 2 mm max 7 2 mm max J OPERATION The alarm outputs of a model with an alarm functio...

Page 27: ...Model G3PA G3PB G3NH G3NA G3NE G3B Appear ance SSRs connected in parallel E5AK E5EK T 8 pcs E5CK T 4 pcs E5AK E5EK T 8 pcs E5CK T 4 pcs E5AK E5EK T 5 pcs E5CK T 2 pcs E5AK E5EK T 2 pcs E5CK T 1 piece...

Page 28: ...8 00 Specifications subject to change without notice Printed in U S A OMRON ELECTRONICS INC One East Commerce Drive Schaumburg IL 60173 1 800 55 OMRON OMRON CANADA INC 885 Milner Avenue Scarborough On...

Reviews: