background image

E5CK-T

  E5CK-T

181

J

AFTER TURNING POWER ON

Determine the I/O specifications of the Process Controller in setup
mode.

Power ON

Process value

1 s min.

1 s min.

Input type

Temperature input

Current/Voltage input

°

C/

°

F

selection

Scaling
upper limit

Scaling
lower limit

Decimal point

Parameter initialize

From next page

To next page

prgn

J

INPUT TYPE

Set the code according to the following table. Default is
 “2: K1 thermocouple.”

Platinum Resistance Thermometer

Set 

Input type

Set 
value

Input type

0

JPt100

–199.9 to 650.0 (

°

C)

/–199.9 to 999.9 (

°

F)

Platinum
resistance

1

Pt100

–199.9 to 650.0 (

°

C)

/–199.9 to 999.9 (

°

F)

thermometer

2

K1

–200 to 1,300 (

°

C)

/–300 to 2,300 (

°

F)

Thermocouple

3

K2

0.0 to 500.0 (

°

C)

/0.0 to 900.0 (

°

F)

4

J1

–100 to 850 (

°

C)

/–100 to 1,500 (

°

F)

5

J2

0.0 to 400.0 (

°

C)

/0.0 to 750.0 (

°

F)

6

T

–199.9 to 400.0 (

°

C)

/–199.9 to 700.0 (

°

F)

7

E

0 to 600 (

°

C)

/0 to 1,100 (

°

F)

8

L1

–100 to 850 (

°

C)

/–100 to 1,500 (

°

F)

9

L2

0.0 to 400.0 (

°

C)

/0.0 to 750.0 (

°

F)

10

U

–199.9 to 400.0 (

°

C)

/–199.9 to 700.0 (

°

F)

11

N

–200 to 1,300 (

°

C)

/–300 to 2,300 (

°

F)

12

R

0 to 1,700 (

°

C)

/0 to 3,000 (

°

F)

13

S

0 to 1,700 (

°

C)

/0 to 3,000 (

°

F)

14

B

100 to 1,800 (

°

C)

/300 to 3,200 (

°

F)

15

W

0 to 2,300 (

°

C)

/0 to 4,100 (

°

F)

16

PLII

0 to 1,300 (

°

C)

/0 to 2,300 (

°

F)

17

4 to 20 mA

Current input

18

0 to 20 mA

19

1 to 5 V

Voltage input

20

0 to 5 V

21

0 to 10 V

Summary of Contents for E5CK-AA1-500 AC100-240

Page 1: ...H High accuracy 100 ms sampling for analog input H Conforms to international EMC and safety standards H 24V AC DC type also available H 3 year warranty RC Ordering Information Order control output boa...

Page 2: ...DE0106 part 100 E5CK T 1 E53 COV07 Software For setup and monitoring requires optional computer communications board All 1 SYS CONFIG V2 0 Temperature Ranges Platinum Resistance Thermometer Input swit...

Page 3: ...units of 0 1 FS Integral reset time I 0 to 3 999 s in units of 1 s Derivative rate time D 0 to 3 999 s in units of 1 s Control period 1 to 99 s in units of 1 s Manual reset value 0 0 to 100 0 in unit...

Page 4: ...contact discharge level 2 8kV air discharge level 3 Immunity RF interference ENV50140 10V m amplitude modulated 80 MHz to 1 GHz level 3 10 V m pulse modulated 900 MHz Immunity Conducted Disturbance E...

Page 5: ...rd model set up the output boards for control outputs 1 and 2 before mounting the Controller 2 On a position proportional model the relay output board is already set so this setup operation is unneces...

Page 6: ...74 Dimensions Unit mm inch J E5CK T 60 2 36 min Panel Cutouts 65 2 56 min 48 1 89 58 2 28 13 3 0 52 100 3 94 53L x 53W 44 8 X 44 8 J ACCESSORIES ORDER SEPARATELY Terminal Cover E53 COV07 44 3 1 74 44...

Page 7: ...arefully pull the internal mechanism from the housing Refer to the drawing below J SETTING UP THE OUTPUT BOARD 1 Two rectangular holes are provided on the power board right side of Controller Fit the...

Page 8: ...cm Adapter Panel Watertight packing Input Jumper Setting Note The jumper is factory set to TC S PT temperature input Set the jumper to temperature voltage or current input according to the sensor con...

Page 9: ...s from external noise Solderless terminals are recommended when wiring the Controller Tighten the terminal screws using a torque no greater than 0 78 N S m or 8 kgf S cm max Be careful not to tighten...

Page 10: ...eter inputs set the inputs to a common position TC PT as the temperature input Control Output Terminal numbers 11 and 12 are for control output 1 OUT1 The five output types and internal equalizing cir...

Page 11: ...8 7 6 13 14 11 12 3 2 Relay specifications are as follows SPST NO 250 VAC 1 A Option Terminal numbers 1 13 and 14 are valid only when the option board is set in the Controller The following four conn...

Page 12: ...ay key sp0 0 4 Set the target value to 50 Target value Display key 50 sp0 Step number display 5 Press the Display Key to shift to the display for the time of Step 0 Time parameter for step 0 Step time...

Page 13: ...C 199 9 to 999 9 F Platinum resistance 1 Pt100 199 9 to 650 0 C 199 9 to 999 9 F thermometer 2 K1 200 to 1 300 C 300 to 2 300 F Thermocouple 3 K2 0 0 to 500 0 C 0 0 to 900 0 F 4 J1 100 to 850 C 100 t...

Page 14: ...and 2 and auxiliary outputs 1 and 2 The assignment destination of each output function is restricted Refer to the tables provided under the headings Standard Models and Position Proportionate Models...

Page 15: ...ce deviation X SP ON OFF X SP ON OFF 7 Lower limit alarm with standby sequence deviation X SP ON OFF X SP ON OFF 8 Absolute value upper limit alarm X 0 ON OFF 0 X ON OFF 9 Absolute value lower limit a...

Page 16: ...e alarm 1 to 3 open in alarm parameters setup mode Factory setting is close in alarm n o J PARAMETER OPERATION LIST Switching to modes other than manual or protect mode is carried out using the mode s...

Page 17: ...AT auto tuning set up the control period change PID parameters and set alarm values Level 2 Mode This is the auxiliary mode for adjusting control In this mode you can set the parameters for limiting...

Page 18: ...tors remote SP in the local SP mode Set Point During SP Ramp Monitors the set point when the SP ramp function is used J PROTECT MODE Press twice for 1 s min Security Key protect To level 0 Press twice...

Page 19: ...arameter of the Controller in standard control is 0 Hysteresis Heat Available when the Controller is in ON OFF control For heating cooling control Hysteresis Cool Available when the Controller is in O...

Page 20: ...ut Shift Lower Limit Available if the input type is a thermocouple or platinum resistance thermometer See Input Shift For models E5AK EK T only Open Close hysteresis Standby time Input Shift Temperatu...

Page 21: ...are used J OPTION MODE Event Input Assignment 1 Available for the event input function Event Input Assignment 2 Available for the event input function For models E5AK E5EK T only Event Input Assignme...

Page 22: ...t value step 0 time step 1 target value and step 1 time The step target value can be set within a range between the lower and upper target value limits The default value is zero The step time can be s...

Page 23: ...p 0 Set the ON OFF timing with the timing signal 1 2 ON time and time signal 1 2 OFF time parameters in Program mode ON Conditions If the ON time is shorter than the OFF time the signal will be reset...

Page 24: ...mal the probable cause may be external noise affecting the control system Check for external noise Operation at Error Control output functions turn OFF 2 mA max at 4 to 20 mA output and output equival...

Page 25: ...ol continues allowing normal operation Motor Calibration Error Displayed on the No 2 Display Meaning Motor calibration has ended with an error Action First correctly connect the wiring for the potenti...

Page 26: ...Unit must be approximately 0 78 N S m or 8 kgf S cm Use the following type of solderless terminals for M3 5 screws 7 2 mm max 7 2 mm max J OPERATION The alarm outputs of a model with an alarm functio...

Page 27: ...Model G3PA G3PB G3NH G3NA G3NE G3B Appear ance SSRs connected in parallel E5AK E5EK T 8 pcs E5CK T 4 pcs E5AK E5EK T 8 pcs E5CK T 4 pcs E5AK E5EK T 5 pcs E5CK T 2 pcs E5AK E5EK T 2 pcs E5CK T 1 piece...

Page 28: ...8 00 Specifications subject to change without notice Printed in U S A OMRON ELECTRONICS INC One East Commerce Drive Schaumburg IL 60173 1 800 55 OMRON OMRON CANADA INC 885 Milner Avenue Scarborough On...

Reviews: