E5CK-T

  E5CK-T

182

J

PARAMETER INITIALIZE

Parameter initialization sets all parameters to default values
except for the input type, scaling upper limit, scaling lower limit,
decimal point, and 

°

C/

°

F selection parameters.

To previous page

From previous page

Control output 1
assignment (Not
displayed by the
E5

j

K-TPRR2)

Control output 2
assignment (Not
displayed by the
E5

j

K-TPRR2)

Auxiliary output 1
assignment

Output
assignment

Auxiliary output 2
assignment (Not
displayed by the
E5CK)

Alarm 1 type

Alarm 1
open in
alarm

Alarm 2 type

Alarm type

Alarm 2
open in
alarm

Alarm
1, 2, or
3 is not
set.

Alarm 3 type

Alarm 3
open in
alarm

Direct/Reverse
operation

J

OUTPUT ASSIGNMENTS

Signals available as allocated outputs are the control output
(heat), control output (cool), alarm 1, alarm 2, alarm 3, LBA. The
auxiliary outputs of the Process Controller cannot be used as
control outputs. The E5CK-T does not have a heater burnout
alarm (HBA).

Control output (heat), control output (cool), alarm 1, alarm 2,
alarm 3, LBA, error 1 (input error), and error 2 (A/D converter
error) output functions are available. These functions are
assigned to control outputs 1 and 2 and auxiliary outputs 1 and 2.

The assignment destination of each output function is restricted.
Refer to the tables provided under the headings, Standard
Models and Position-Proportionate Models.

J

STANDARD MODELS

Assignment destination

Control output

Auxiliary output

1

2

1

Control output (heat)

Yes

Yes

---

Control output (cool)

Yes

Yes

---

Alarm 1

Yes

Yes

Yes

Alarm 2

Yes

Yes

Yes

Alarm 3

Yes

Yes

Yes

LBA

Yes

Yes

Yes

Error 1: Input error

---

---

Yes

Error 2: A/D converter error

---

---

Yes

With control output (cool), the conditions for switching from
standard control to heating and cooling control are reached
when the output function is assigned at the cooling side during
heating and cooling control.

In other words, heating and cooling control is carried out when
control output (cool) is assigned, and standard control is carried
out when output is not assigned.

LBA

The LBA (loop break alarm) function is available when it is
assigned as an output. The LBA function is not available when a
memory or A/D converter error results.

LBA is a function for determining that an error has occurred
somewhere on the control loop and outputting an alarm when the
process value does not change with the manipulated variable at
a maximum or minimum state. Accordingly, the LBA function can
be used as a means for detecting a malfunctioning control loop.

Summary of Contents for E5CK-AA1-500 AC100-240

Page 1: ...H High accuracy 100 ms sampling for analog input H Conforms to international EMC and safety standards H 24V AC DC type also available H 3 year warranty RC Ordering Information Order control output boa...

Page 2: ...DE0106 part 100 E5CK T 1 E53 COV07 Software For setup and monitoring requires optional computer communications board All 1 SYS CONFIG V2 0 Temperature Ranges Platinum Resistance Thermometer Input swit...

Page 3: ...units of 0 1 FS Integral reset time I 0 to 3 999 s in units of 1 s Derivative rate time D 0 to 3 999 s in units of 1 s Control period 1 to 99 s in units of 1 s Manual reset value 0 0 to 100 0 in unit...

Page 4: ...contact discharge level 2 8kV air discharge level 3 Immunity RF interference ENV50140 10V m amplitude modulated 80 MHz to 1 GHz level 3 10 V m pulse modulated 900 MHz Immunity Conducted Disturbance E...

Page 5: ...rd model set up the output boards for control outputs 1 and 2 before mounting the Controller 2 On a position proportional model the relay output board is already set so this setup operation is unneces...

Page 6: ...74 Dimensions Unit mm inch J E5CK T 60 2 36 min Panel Cutouts 65 2 56 min 48 1 89 58 2 28 13 3 0 52 100 3 94 53L x 53W 44 8 X 44 8 J ACCESSORIES ORDER SEPARATELY Terminal Cover E53 COV07 44 3 1 74 44...

Page 7: ...arefully pull the internal mechanism from the housing Refer to the drawing below J SETTING UP THE OUTPUT BOARD 1 Two rectangular holes are provided on the power board right side of Controller Fit the...

Page 8: ...cm Adapter Panel Watertight packing Input Jumper Setting Note The jumper is factory set to TC S PT temperature input Set the jumper to temperature voltage or current input according to the sensor con...

Page 9: ...s from external noise Solderless terminals are recommended when wiring the Controller Tighten the terminal screws using a torque no greater than 0 78 N S m or 8 kgf S cm max Be careful not to tighten...

Page 10: ...eter inputs set the inputs to a common position TC PT as the temperature input Control Output Terminal numbers 11 and 12 are for control output 1 OUT1 The five output types and internal equalizing cir...

Page 11: ...8 7 6 13 14 11 12 3 2 Relay specifications are as follows SPST NO 250 VAC 1 A Option Terminal numbers 1 13 and 14 are valid only when the option board is set in the Controller The following four conn...

Page 12: ...ay key sp0 0 4 Set the target value to 50 Target value Display key 50 sp0 Step number display 5 Press the Display Key to shift to the display for the time of Step 0 Time parameter for step 0 Step time...

Page 13: ...C 199 9 to 999 9 F Platinum resistance 1 Pt100 199 9 to 650 0 C 199 9 to 999 9 F thermometer 2 K1 200 to 1 300 C 300 to 2 300 F Thermocouple 3 K2 0 0 to 500 0 C 0 0 to 900 0 F 4 J1 100 to 850 C 100 t...

Page 14: ...and 2 and auxiliary outputs 1 and 2 The assignment destination of each output function is restricted Refer to the tables provided under the headings Standard Models and Position Proportionate Models...

Page 15: ...ce deviation X SP ON OFF X SP ON OFF 7 Lower limit alarm with standby sequence deviation X SP ON OFF X SP ON OFF 8 Absolute value upper limit alarm X 0 ON OFF 0 X ON OFF 9 Absolute value lower limit a...

Page 16: ...e alarm 1 to 3 open in alarm parameters setup mode Factory setting is close in alarm n o J PARAMETER OPERATION LIST Switching to modes other than manual or protect mode is carried out using the mode s...

Page 17: ...AT auto tuning set up the control period change PID parameters and set alarm values Level 2 Mode This is the auxiliary mode for adjusting control In this mode you can set the parameters for limiting...

Page 18: ...tors remote SP in the local SP mode Set Point During SP Ramp Monitors the set point when the SP ramp function is used J PROTECT MODE Press twice for 1 s min Security Key protect To level 0 Press twice...

Page 19: ...arameter of the Controller in standard control is 0 Hysteresis Heat Available when the Controller is in ON OFF control For heating cooling control Hysteresis Cool Available when the Controller is in O...

Page 20: ...ut Shift Lower Limit Available if the input type is a thermocouple or platinum resistance thermometer See Input Shift For models E5AK EK T only Open Close hysteresis Standby time Input Shift Temperatu...

Page 21: ...are used J OPTION MODE Event Input Assignment 1 Available for the event input function Event Input Assignment 2 Available for the event input function For models E5AK E5EK T only Event Input Assignme...

Page 22: ...t value step 0 time step 1 target value and step 1 time The step target value can be set within a range between the lower and upper target value limits The default value is zero The step time can be s...

Page 23: ...p 0 Set the ON OFF timing with the timing signal 1 2 ON time and time signal 1 2 OFF time parameters in Program mode ON Conditions If the ON time is shorter than the OFF time the signal will be reset...

Page 24: ...mal the probable cause may be external noise affecting the control system Check for external noise Operation at Error Control output functions turn OFF 2 mA max at 4 to 20 mA output and output equival...

Page 25: ...ol continues allowing normal operation Motor Calibration Error Displayed on the No 2 Display Meaning Motor calibration has ended with an error Action First correctly connect the wiring for the potenti...

Page 26: ...Unit must be approximately 0 78 N S m or 8 kgf S cm Use the following type of solderless terminals for M3 5 screws 7 2 mm max 7 2 mm max J OPERATION The alarm outputs of a model with an alarm functio...

Page 27: ...Model G3PA G3PB G3NH G3NA G3NE G3B Appear ance SSRs connected in parallel E5AK E5EK T 8 pcs E5CK T 4 pcs E5AK E5EK T 8 pcs E5CK T 4 pcs E5AK E5EK T 5 pcs E5CK T 2 pcs E5AK E5EK T 2 pcs E5CK T 1 piece...

Page 28: ...8 00 Specifications subject to change without notice Printed in U S A OMRON ELECTRONICS INC One East Commerce Drive Schaumburg IL 60173 1 800 55 OMRON OMRON CANADA INC 885 Milner Avenue Scarborough On...

Reviews: